The user must supply the following components depending upon the application. This
equipment includes:
Current transformers, 5 Amps
Potential transformers
Fuses (1 Amp each) for each voltage lead connected to the Terminal Assembly.
A fuse (1 Amp) for the common or return line for the voltage lead on the
Terminal Assembly.
A CT shorting block for each current transformer (CT) connection used on the
Terminal Assembly when used with external CTs.
IC694PSK001
PSM System. Includes a PSM module, a Terminal Assembly and two interface
cables
IC694PSM001
Replacement PSM module
IC694ACC200
Replacement Terminal Assembly
IC694CBL200
One replacement 2m (6.56 ft.) interface cable
IC694ACC201
PSM replacement parts:
two finger guards
four thumb screws
one relay connector
two grounding lug nuts
PACSystems* RX3i Power Sync and Measurement System – February 2013