GE PACSystems RX3i User Manual page 80

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

3
ANSI Protection Tab
Note that synchronization is an option in 3-phase mode, so the ANSI 25 parameters can
be left at their default values, or changed to suit the application. The Breaker Delay value
of 125ms allows the PSM to perform a rotating phase angle synchronization, closing the
contacts right at 0º when the grid frequencies are held steady during the sync process.
PACSystems* RX3i Power Sync and Measurement System – February 2013
3-36
GFK-2749