Password Protection (Default = 0) - Siemens SITRANS LG200 Series Instruction Manual

Table of Contents

Advertisement

Output (% Output)
% Output measurement derived from 20 mA span.
Values (View only)
Loop Value (Loop)
Loop value (in mA).
Values (View only)
Volume (if Measurement Type set to Lvl&Vol)
Displays volume value in selected units.
Values (View only)
Ifc Level (if Measurement Type set to Intrface)
Displays interface value in selected units.
Values (View only)
Ifc Vol (if Measurement Type set to Ifc&Vol)
Displays interface and volume value in selected units.
Values (View only)
To return to RUN mode, scroll to *Status*.
Parameter Listing

Password Protection (Default = 0)

The SITRANS LG200 transmitter is password protected to restrict access to parts of the
menu structure that affect the operation of the system.
The LG200 uses three levels of password: user, factory and superuser passwords.
User password
In Program Mode, when the proper user password is entered, an exclamation point (!) is
the last character of the first line of the display. The user password can be changed to
any numerical value up to 255. The password is required whenever configuration values
are changed.
The default user password is 0. Enter a new password in the last step of the configuration
menu. With a password of 0, the transmitter is no longer password protected and any
value in the menu can be altered without entering a confirming password, except
diagnostic values. The device remains unprotected for five minutes without a button
pressed, and then the password protection set is applied.
Page 58
% Output xx.x %
Loop xx.xx mA
Volume xxx.x (liters or gallons)
IfcLvl xxx.x (in, cm, ft, m)
IfcVol xxx.x (liters or gallons)
SITRANS LG200 – INSTRUCTION MANUAL