Hart Output - Siemens SITRANS LG200 Series Instruction Manual

Table of Contents

Advertisement

Dielectric Range for probe models.
1.4- 1.7
Sensitivity (Senstvty)
Allows fine gain adjustment for single rod probes. This parameter requires a user
password for single rod probes. (User or Superuser password)
Values
Sensitivity adjustment is only available to technical support users for coaxial and twin rod
probe applications.

Hart Output

Loop Control (Loop Ctrl)
Select variable to control loop current (mA output). (User password)
Values
Page 64
1.7-3
7ML1301-1, 7ML1301-2, 7ML1301-3, 7ML1301-4
7ML1303-1, 7ML1303-2, 7ML1303-1J, 7ML1303-1D,
7ML1303-1B, 7ML1302-1, 7ML1302-3, 7ML1302-2(1.9 to 100)
Enter value upward or downward to sense liquid surface.
(Default: 55, probe model dependent)
Lvl (Level) (Default)
Lvl&Vol (Volume)
Ifc (Interface Level), [7ML1301-6 (7xT-x) only]
Ifc&Vol (Interface Volume), [7ML1301-6 (7xT-x) only]
SITRANS LG200 – INSTRUCTION MANUAL
3-10
10-100
7ML1301-5,
7ML1304-1
7ML1301-6
(Upper Liquid
Layer 1.4-5,
Interface Liquid
Layer 15 to 100)
7ML1304-2 (4 to 100)
7ML19985KA02