Siemens SITRANS LG200 Series Instruction Manual page 72

Table of Contents

Advertisement

Attach a current meter into the loop. Adjust the trim until the meter reads 20.0 mA. The
value of Trim mA is typically 3266 counts, but will vary from unit to unit by about ±100
counts.
Loop Test mA (Loop Tst)
Enter value to adjust level reading. Used to adjust for mounting/installation effects with
single rod probes. A value can be programmed to test connected equipment. (User
password)
Values
Level Ticks (Lvl Ticks)
Time of flight from reference point to level signal return measured in multiples of 2. 1 4
Count may exceed display capabilities (9999) on long probes.
Values
Interface Ticks (Ifc Ticks)
Time of flight through upper liquid.
Values
Medium
Applicable only when Ifc, Ifc&Vol selected. Provides information on interface layer, based
on analog waveform.
Values (View
Only)
New Password (New Pass)
Displays encrypted value of present password. To retrieve forgotten password, contact
factory with encrypted value. Then enter new password. (User password)
Values
Language (Language)
Language choice for LCD display (factory screens related to steam calibration will always
be displayed in English). (User password)
Values
Page 68
Loop Tst xx.x mA (Range ±20")
LvlTicks Xxxxx (0 to 9999, display dependent)
LvlTicks Xxxxx (0 to 9999, display dependent)
Unknown
Oil only
Thin oil
Thick oil
Dry probe
Default: 0 (Range 0 to 255)
English (Default)
Spanish
French
German
SITRANS LG200 – INSTRUCTION MANUAL
μ
s.
7ML19985KA02