Technical data

3.1
Pump SPF
Submersible black water pump with multi-vane impeller
Information / pump type
Weight
*)
Power P1 / P2
Speed
Operating voltage
Rated current
Max. pumping capacity
Max. pumping height
Max. temperature
Pumping medium
Protection rating
Protection class
Motor protection
Connection type
Connecting cable (10 m)
Type of fuse required (Mono)
Operating mode
*) Version for S1 operation. 2 kg heavier for S3 operation.
Power and pumping height
(1)
(2)
(3)
(4)
3.2
Dimensions, volume
Outer diameter [mm]
Pumping volume [l]
Tank volume [l]
010-695_02
1400
24 kg
1.6 kW / 1.1 kW
1370 rpm
230 V; 50 Hz
7.3 A
38 m³/h
7 m
SPF 1400
SPF 1500
SPF 3000
SPF 4500
Height
Pumping station / Installation and operating instructions
1500
24 kg
1.4 kW / 1.1 kW
3.2 kW / 2.7 kW
1415 rpm
2845 rpm
400 V; 50 Hz
2.7 A
40 m³/h
8 m
40 °C
IP68 (3 mWs/48 h)
I
external
Direct connection
7 x 1.5 mm²
See control unit operating instructions
S1 / S3
See instructions for engineering cham-
ber LW 1000 (part. no. 010-701)
3000
4500
25 kg
26 kg
4.5 kW / 3.7 kW
2845 rpm
5.4 A
7.5 A
47 m³/h
55 m³/h
16 m
20 m
1200
160
335