UPS5000-S-1200 kVA
User Manual
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0001-1
Mains voltage
abnormal
Issue 08 (2020-12-15)
NO TE
This table lists only common alarms. For more information, contact Huawei technical
support.
Severity
Minor
Copyright © Huawei Technologies Co., Ltd.
B
Cause
● Cable
connections
are incorrect.
● The mains is
not normal.
● The power
module is
faulty.
● The output or
battery is
incorrectly
grounded.

B Alarm List

Alarm List
Solution
1. Check whether cables to
mains are disconnected,
loose, or incorrectly
connected.
2. If cable connections are
correct, measure the mains
voltage with a multimeter.
If the mains voltage
exceeds 280 V, the mains
input is not normal; if the
mains voltage is less than
272 V, the sampling circuit
of the power module is not
normal. Replace the faulty
module.
3. Check whether the output
or battery is incorrectly
grounded.
215