Huawei UPS5000-S User Manual page 161

1200 kva
Hide thumbs Also See for UPS5000-S:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Capacitor
failure
detection
upper limit
(A)
Capacitor
failure
detection
lower limit
(A)
Bypass Settings
Item
BPM mode
upon BPM
overtemp.
BPM cur. eql.
Function
Bypass
current eql.
threshold
Lightload
BPM cur. eql.
Detect
Issue 08 (2020-12-15)
Description
-
-
Description
Specifies whether to start
bypass mode when
overtemperature occurs.
When paralleling, whether
the active current sharing is
allowed for bypass.
When BPM cur. eql.
function is set to Enable and
the maximum bypass load
rate in the parallel system
exceeds this threshold, the
bypass current equalization
function is enabled.
Enable or disable the light
load bypass current
imbalance alarm. If this
parameter is set to Enable,
the load is light (less than
30% load), and the load rate
of a certain rack is less than
10%, the system will
generate a bypass current
imbalance alarm and cannot
enter the ECO mode. If this
parameter is set to Enable,
the preceding detection is
not performed. Whether the
bypass current is imbalanced
does not affect the ECO
bypass mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
13.0
10.0–13.0
2.5
0.0–2.5
Default Value
Value Range
Enable
Disable,
Enable
Enable
Disable,
Enable
40%
40%, 50%,
60%, 70%,
80%
Enable
Disable,
Enable
152