UPS5000-S-1200 kVA
User Manual
6.2.1 Precautions for Battery Maintenance
●
●
●
●
●
●
6.2.2 Monthly Maintenance
Table 6-4 Monthly maintenance
Item
Battery
management
alarm
Battery
appearance
Battery
operating
temperature
Issue 08 (2020-12-15)
Before battery maintenance, get the tools, such as handles, insulated. Do not
place other objects on the top of batteries.
Never use any organic solvent to clean batteries.
Never try to remove the safety valve or pour anything into batteries.
Never smoke or have an open flame around batteries.
After battery discharge, charge the battery in time to maintain a good service
life.
Only professionals are allowed to perform the maintenance tasks.
Expected Result
No battery management
alarm is generated.
1. The surface is clean and
tidy without stains.
2. The battery terminals are
intact.
3. Batteries are free from
damage and cracks.
4. Batteries are free from acid
leakage.
5. Batteries are not deformed
or bulged.
1. The ambient battery
temperature is 25±5°C.
2. The battery operating
temperature is lower than
battery temperature +20°C.
3. Battery charge and
discharge conditions meet
the requirements specified
in the battery
specifications.
Copyright © Huawei Technologies Co., Ltd.
6 Routine Maintenance
Troubleshooting
Identify the cause of an alarm
based on the alarm
information.
If the battery appearance is
abnormal, contact Huawei
technical support.
1. Identify the cause of an
abnormal battery operating
temperature.
2. If the fault persists, contact
Huawei technical support.
201