Step 4 Enter the correct user name and password and click Login.
Figure 5-2 Logging in to the WebUI
Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON,
and confirm the operation to start the inverter.
----End
5.1.4 Powering On Loads
Context
After the inverter starts, the UPS works in normal mode. The Bypass mode alarm
disappears.
Procedure
Step 1 After confirming that the battery strings are properly connected, close the battery
string input circuit breaker. If there are multiple battery strings, close the circuit
breaker for each battery string and then the general circuit breaker between
battery strings and the UPS. The No battery alarm disappears from the MDU.
Step 2 Turn on the system output switch (Q5) to supply power to loads.
----End
5.1.5 (Optional) Setting Parameters for the BCB Box
Prerequisites
A BCB box is installed.
●
Issue 08 (2020-12-15)
NO TE
If the power module receives a startup command when it cannot be started, the startup
command will be kept for 1 minute. If the startup command is not cleared within 1 minute
(for example, other faults occur on the module, or you perform shutdown or rectify faults)
and the module can be started, the module responds to the startup command.
If the power units share battery strings, you need to set BCB box parameters
only on the LCD of power unit 1.