4.2.5.2 RCCMD Event Shutdown and Message Sending

Procedure
Step 1 On the RCCMD client, choose Connections, add the server IP address, and set the
encryption mode to encryption.
Figure 4-73 Setting the MDU IP address and SSL encrypted transmission mode on
the RCCMD client
Step 2 On the MDU WebUI, choose Config. > RCCMD, and set RCCMD function to
Enable.
Step 3 On the WebUI of the MDU, the SSL encryption is set to Enable by default and
does not need to be set. If the RCCMD client is set to the unencrypted mode, you
need to set the SSL encryption to Disable on the server WebUI.
Step 4 Configure events. If you set the job type to RCCMD Message under Inverter on,
specify the IP address and port of the RCCMD client. The port is 6003 by default. If
you need to modify the port, modify the port on the RCCMD client at the same
time to keep them the same. Enter the message to be sent and set the message
sending mechanism. For example, set it to Immediately, once.
Issue 08 (2020-12-15)
NO TE
● If encryption is disabled, you do not need to select the encrypted transmission.
● All configurations take effect only after restart.