Huawei UPS5000-S User Manual page 134

1200 kva
Hide thumbs Also See for UPS5000-S:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Input Settings
Figure 4-27 Input settings
Item
D.G. mode
D.G. power
limiting (kVA)
D.G. charger
power ratio
(%)
Input cur.
limiting
Input cur.
limiting ratio
(%)
Issue 08 (2020-12-15)
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters
the D.G. mode when a D.G. is
detected over dry contacts.
Set these two parameters to
control the valid input
current and limiting input
current, which prevents load
impact and facilitates better
cooperation between the
UPS and the D.G.
Specifies whether to enable
or disable input current
limiting to protect
generators.
Limits the input current to
protect the D.G.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable,
Enable
800
0 to 5000
100
0–100
Disable
Disable,
Enable
200
50–200
125

Advertisement

Table of Contents
loading

Table of Contents