Visual inspection

Inspect the product and cables for visible external damage and note the operating status display, where appli-
cable. In the event of damage, notify your installation engineer. Repairs may only be carried out by authorised
electricians.
DANGER
Dangerous voltage due to two operating voltages
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. The dis-
charge time of the capacitors is up to 5 minutes.
1. Only appropriately qualified electricians authorized by the mains supply network operator are permitted to
open and maintain the device.
2. Before opening the device: Disconnect the AC and DC side and wait at least 5 minutes.
NOTE
There are components within the housing that may only be repaired by our customer service team.
1. Do not attempt to rectify faults that are described here (in the troubleshooting chapter). Get in touch with
our customer service team. Only carry out maintenance activities that are described here.
2. Log each maintenance activity in the "Service" menu item: "Service log" (exception: "User" interface) [See
section 9.4.2} Page 49]
3. The device should be checked for proper operation by a qualified electrician at regular intervals. Always
contact the service team of the system manufacturer if you encounter any issues.
11.2

Cleaning

11.2.1 Cleaning the housing
CAUTION
Risk of damage to the device during cleaning!
1. Do not use compressed air or high-pressure cleaners.
2. Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top of the device on a regular
basis.
3. Remove dust from the ventilation inlets if necessary.
11.2.2 Cleaning the heat sink
WARNING
Risk of burning due to hot surface
Heat sinks become very hot during operation.
1. Never touch the heat sinks after starting up the device.
2. Wait until a cooling time of at least 10 minutes has elapsed before starting the cleaning process.