Manual
7.4

Making the electrical connections

NOTE
Select conductor cross-section, safety type and safety value in accordance with the following basic
conditions:
Country-specific installation standards; power rating of the device; cable length; type of cable installation; local
temperature
NOTE
All electrical installations must be carried out in accordance with local electrical standards and con-
form to the National Electrical Code® ANSI / NFPA 70 or the Canadian Electrical Code® CSA C22.1.
This document does not replace any local, federal or national laws, regulations or regulations that apply to the
installation and use of the product, and is not intended to replace them, including the applicable electrical
safety regulations.
All installations must conform to the laws, regulations and standards that are applicable in the country of in-
stallation. KACO new energy does not assume any responsibility for compliance or lack of compliance with such
laws or codes in connection with the installation of the product.
7.4.1
Supply line and fuse requirements
DC-side
Max. cable cross-section
Min. cable cross-section
Diameter of cable for cable fitting
Cable lug dimension b width max.
Length of insulation to be stripped off
Recommended cable type
Cable lug Ø connection bolt
Tightening torque
Fitting for DC connection
Torque for cable fitting
AC-side
Max. cable cross-section
Min. cable cross-section
Diameter of cable for cable fitting
Length of insulation to be stripped off
Cable lug Ø connection bolt
Tightening torque
Connection type
Cable lug dimension w - maximum width
Ground conductor connection
Ground conductor connection tightening torque
Electrical protection in installation (provided by the cus-
tomer)
Fitting for AC connection
Torque for cable fitting
Interfaces
Diameter of cable for cable fitting
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 US
Installation | 7
450 kcmil
acc. to local installation standards
0,63 - 1,10 inch
1,65 inch
Depending on the ring cable lug
solar cable
Bore for M10 screw
265.50 In-Ibs
M40
65 In-Ibs
450 kcmil
acc. to local installation standards
0,63 - 1,10 inch
Depending on the ring cable lug
Bore for M10 screw
265.50 In-Ibs
Cable lug
1,65 inch
M10
88.5 In-Ibs
250A (preliminary)
M40
65 In-Ibs
(2x) 0,31 - 0,67 inch
Page 23