Kaco blueplanet 3.0TL3 Series Manual

Kaco blueplanet 3.0TL3 Series Manual

Hide thumbs Also See for blueplanet 3.0TL3 Series:
Table of Contents

Advertisement

Manual
nEnglish translation of German original
Authorised electrician
Important safety instructions
These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all
times.
KACO blueplanet 3.0TL3
KACO blueplanet 4.0TL3
KACO blueplanet 5.0TL3
KACO blueplanet 6.5TL3
KACO blueplanet 7.5 TL3
KACO blueplanet 8.6TL3
KACO blueplanet 9.0TL3
KACO blueplanet 10.0TL3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the blueplanet 3.0TL3 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Kaco blueplanet 3.0TL3 Series

  • Page 1 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3 Manual nEnglish translation of German original Authorised electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
  • Page 2 Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication, in whole or in part, requires the written permission of KACO new energy GmbH. KACO warranty For current warranty conditions contact your system integrator.
  • Page 3: Table Of Contents

    Manual Photovoltaic feed-in inverter Contents General information............ 4 Controls..............  33 About this document.......... 4 User interface ............  35 More information............ 4 Menu structure ............  36 Layout of Instructions.......... 5 Monitoring the device ..........  51 Identification .............  6 Performing a firmware update .........
  • Page 4: General Information

    Storing the documents These instructions and other documents must be stored near the system and be available at all times. ž The current version of the operating Instructions can be downloaded from www.kaco-newenergy.com. English translation of German original This document has been produced in several languages. The German-language version is the original version. All other language versions are translations of the original version.
  • Page 5: Layout Of Instructions

    2 Additional action sequence ð Interim result of the action » End result KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 5 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 6: Identification

    ž Knowledge of applicable standards and directives. ž Knowledge and adherence to this document with all safety notices. Page 6 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 7: Safety

    The device is intended for indoor and outdoor applications and may only be used in countries for which it has been ap- proved or for which it has been released by KACO new energy and the grid operator. Country...
  • Page 8: Protection Features

    250V. Page 8 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 9: Description Of The Device

    The potential-free relay contact closes as soon as there is a fault during operation. You use this function, for example, to signal a fault visually or acoustically. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 9...
  • Page 10 Digital inputs You can extend the unit with additional digital inputs by means of an extension module (available from KACO customer service). This can be used to connect a ripple control receiver or a protective shutdown system.
  • Page 11: System Layout

    Use the DC isolator switch to disconnect the device from the PV generator. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 11 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 12: Technical Data

    ISCmax of the inverter under all foreseeable conditions. In no condition the design may result in a greater short cir- cuit current than ISCmax of the inverter.Designing the PV generator [See section 7.5.4} Page 26]. Page 12 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 13: General Data

    III / III category Grid monitoring Country-specific Distribution system TN-C-System, TN-C-S-System, TN-S-System, TT-System KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 13 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 14: Environmental Data

    Protection rating (KACO installa- IP65 / NEMA 4 tion location) Humidity range (non-condens- 100% ing) [%] Page 14 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 15: Transportation And Delivery

    Outer contour Slot Fig. 7: Form pattern Tab. 2: Key and description of tool codes KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 15 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 16: Assembly And Preparation

    ž Must be flame resistant ž Minimum clearances to be observed during installation: [See figure 13] [} Page 18] Page 16 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 17: Unpacking The Device

    5 Remove device from the packaging. 6 Place the protective packaging back into the carton. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 17 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 18: Fastening The Mount

    NOTE: Make sure that the mount is oriented correctly. » Proceed with the installation of the device. Page 18 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 19: Installing And Securing The Device

    NOTE: Alternatively: At this point, the screw described above can be replaced by a special screw as anti-theft pro- tection. » Device is installed. Proceed with the electrical installation. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 19 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 20 Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installation. › Immediately remove any moisture from the housing. Page 20 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 21: Installation

    Country-specific installation standards; power rating of the device; cable length; type of cable installation; local temperature KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 21 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 22: Connecting The Device To The Power Grid

    1 Slide the cable fitting over the cable. 2 Select seal according to cable diameter used. Page 22 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 23 If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm in the “Parameters” menu Menu [See section 9.4.1} Page 36]. For questions regarding the appropriate type, please contact the installer or our KACO new energy cus- tomer service.
  • Page 24: Connect Pv Generator To Device

    The threshold value from which the insulation monitor reports an error can be set in the “Parameters” menu. Page 24 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 25 1 PV generator parallel on both MPP tracker tracker is deactivated trackers KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 25 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 26 › Do not connect any strings with a ground fault to the device. Page 26 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 27: Creating Equipotential Bonding

    » The housing is included in the equipotential bonding. Fig. 32: Additional grounding point 1 Earthing bolt KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 27 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 28: Connecting The Interfaces

    » Proceed with the connection. ernet cable Cable fitting for pass the sig- nal cable Page 28 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 29 Li2YCY (twisted pair) grey for dry and damp indoor spaces, 2 x 2 x 0.5 mm² KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 29 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 30 The digital input of the device is intended for connection of a Powador-protect. When using devices from other manufacturers or in combination with KACO inverters, interface switches as a minimum must be used for shutting down devices from other manufacturers.
  • Page 31: Sealing The Connection Area

    3 Set the DC isolator switch to “1”. » Put the device into operation. Fig. 38: Close the connection cover KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 31 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 32: Commissioning

    10 minutes. The self-test report contains the nominal tripping values, the actual tripping values and the correspond- ing tripping times. Page 32 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 33: Configuration And Operation

    *) The waiting period ensures that the generator voltage continuously remains above the power delivery limit of 200 V. For country-specific waiting periods see our website. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 33...
  • Page 34 Opening a menu item or a setting F Use the right arrow button and the Enter button. Page 34 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 35: User Interface

    If no button is pressed for an adjustable period of time, the backlighting switches off again. You can also activ- ate or disable the backlighting permanently. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 35...
  • Page 36: Menu Structure

    Displays the current value of the external power limitation by the grid operator. Page 36 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 37 Decimal separator F Select decimal sign for export of saved operating data. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 37 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 38 3 Alternatively: Permanently activate or disable the backlighting by selecting "On" or "Off". Page 38 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 39 F Set network port. Connection status Indicates the status of the network connection. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 39 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 40 2 Where applicable, set period from occurrence of the fault to shut- down of the device. Page 40 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 41 LC display, then the value of f is automatically set to the value of max. f>. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 41 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 42 4 Confirm the entry with the Enter button. Fault ride-through NOTE: The device doesn't support dynamic grid stabilization (Fault Ride-Through). Page 42 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 43 (per thousand) /minute (if mode "1" or mode "2" is active. This menu option is displayed permanently for IT and IL!). KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 43 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 44 1s – 120 s sponse corresponds to a first-order filter (PT-1) with settling time = 5Tau. Page 44 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 45 NOTE: Grid operators require shutdown of the device with standalone grid detection. F Further parameterisation is possible via the web interface. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 45 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 46 Priority – Reactive cur- F Select a control process. rent limitation | Active current priority Page 46 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 47 F Set min. and max. switch-on voltage after grid monitoring. after grid failure Max conn. voltage after grid failure KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 47 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 48 Page 48 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 49 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 49 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 50 230V – 276V 1 Specify the deactivation threshold. Page 50 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 51: Monitoring The Device

    1 When using a DHCP server: Activate DHCP. 2 For manual configuration (DHCP off): KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 51 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 52 Regardless of the display data selected in the “Choose view” area, an export file always contains all meas- urement data and yield data available for the selected period. Page 52 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 53: Performing A Firmware Update

    3 When an error occurs, the update process must be repeated. You can check to see if the update was successful in the menu: KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 53...
  • Page 54: Access Via Modbus

    3 Set up the Port for access. [Default: 502] » Access via Modbus enabled. Page 54 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 55: Specifications

    (PT-1) with a time constant of Tau=200ms. The specified displacement factor may be configured in the display or via communication, via KACO RS485 protocol and MODBUS/SunSpec. If the applicable grid code requires the cos-φ response to set point by a defined gradient or settling time slower than the configured Tau=200ms, this gradient or settling time must be implemented in the plant control system.
  • Page 56 5 Tau. Lock-in voltage The control is activated above this voltage. 23V – 287V Page 56 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 57 Minimum cos φ in over-excited operating mode (charge). Minimum cos φ in over-excited operating mode (charge). KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 57 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 58: Active Power Regulation

    [WMaxLimPct_RvrtTms] communication failure. Settling time 1000 [ms] Non-configurable settings 1 s. [VArPct_RmpTms] Page 58 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 59 In this case, P(U) control is available for making optimum use of the capacity of the upstream grid. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 59...
  • Page 60 Page 60 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 61 52] [} Page 61]. The drop s can be transformed into a gradient g in accordance with equation 4 [See figure 53] [} Page 61]. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 61 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 62 Power reference for power adjustment as in equation 6 and equation 7 with underfrequency for overfrequency incidents. Actual power | Nominal power Page 62 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 63 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 63 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 64: Frt

    If a reduction in power occurs, the power is brought back up to the pre-fault level within 100 ms of the voltage returning. Page 64 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 65 The pre-fault voltage is calculated as a 1-min mean value. Fig. 59: Formula no. 3 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 65 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 66 Constant k negative se- quence swell k 0 – 10 Page 66 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 67: Other Grid-Supporting Functions That Are Effective In The Case Of Active Power

    KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 67 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 68: Advanced Islanding Detection

    Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Considering the fact that all KACO TL3 inverters have a semi-circular P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power be- cause an apparent power reserve is not available.
  • Page 69 In the event of active stage 1, the device switches to zero current mode, and re- starts the infeed after a few 100ms. At stage 2, the device has shut down and the set reconnection conditions apply. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 69...
  • Page 70: Maintenance And Troubleshooting

    1 Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top of the device on a regular basis. Page 70 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 71: Replacing The Fan

    » The replacement fan is ready for operation. » Switch unit on. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 71 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 72: Shutting Down For Maintenance / Troubleshooting

    Fig. 67: Unplugging the plug con- nector 3 Disconnect the DC connector from the DC socket. Screwdriver Latch Page 72 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 73: Faults

    Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. › If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH Service. ›...
  • Page 74: Fault Messages

    B = Operator’s responsibility ; E = The indicated work may only be carried out by an authorised electrician. ; K = The indic- ated work may only be carried out by a service employee of KACO new energy GmbH! 11.7...
  • Page 75: Troubleshooting

    (RampUp). KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 75 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 76 Grid frequency below the minimum permiss- Notify your author- ible grid frequency set ised electrician. Page 76 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 77 See description in the event of a fault 82 In case of repeated volt. L2 occurrence: Notify your authorised electrician. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 77 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 78 L1 is outside the upper limit value (2-stage in- spection). 108…113 quick shutdowns Page 78 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 79 Safety function of the inverter. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 79 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 80 If fault numbers are displayed on the device but are not listed here, then it is usually necessary to have this looked at by your installation partner. Page 80 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 81: Decommissioning And Dismantling

    7 Open the cable fittings [ W_29 / W_19]. 8 Pull the cables out of the device. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 81 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 82: Disassembling The Device

    F Store the device at a dry location, in accordance with the ambient temperature range Environmental data [See sec- tion 4.3} Page 14]. Page 82 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 83: Disposal

    Packaging: Ensure that the transport packaging is disposed of properly. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 83 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
  • Page 84: Service And Warranty

    Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: ž Device name / serial number ž...
  • Page 85: Appendix

    Unauthorised modifications to the supplied devices and/or any use of the devices that is contrary to their intended use render this Declaration of Conformity null and void. This declaration of conformity is issued under the sole responsibility of KACO new energy GmbH. Neckarsulm, 05/27/2020...
  • Page 86 Carl-Zeiss-Strasse 1 · 74172 Neckarsulm · Germany · Tel. +49 7132 3818-0 · Fax. +49 7132 3818-703 · info@kaco-newenergy.de · www.kaco-newenergy.de...