Summary of Contents for Kaco blueplanet 3.0TL3 Series
Page 1
KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3 Manual nEnglish translation of German original Authorised electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
Page 2
Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication, in whole or in part, requires the written permission of KACO new energy GmbH. KACO warranty For current warranty conditions contact your system integrator.
Manual Photovoltaic feed-in inverter Contents General information............ 4 Controls.............. 33 About this document.......... 4 User interface ............ 35 More information............ 4 Menu structure ............ 36 Layout of Instructions.......... 5 Monitoring the device .......... 51 Identification ............. 6 Performing a firmware update .........
Storing the documents These instructions and other documents must be stored near the system and be available at all times. The current version of the operating Instructions can be downloaded from www.kaco-newenergy.com. English translation of German original This document has been produced in several languages. The German-language version is the original version. All other language versions are translations of the original version.
The device is intended for indoor and outdoor applications and may only be used in countries for which it has been ap- proved or for which it has been released by KACO new energy and the grid operator. Country...
The potential-free relay contact closes as soon as there is a fault during operation. You use this function, for example, to signal a fault visually or acoustically. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 9...
Page 10
Digital inputs You can extend the unit with additional digital inputs by means of an extension module (available from KACO customer service). This can be used to connect a ripple control receiver or a protective shutdown system.
ISCmax of the inverter under all foreseeable conditions. In no condition the design may result in a greater short cir- cuit current than ISCmax of the inverter.Designing the PV generator [See section 7.5.4} Page 26]. Page 12 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
NOTE: Make sure that the mount is oriented correctly. » Proceed with the installation of the device. Page 18 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
NOTE: Alternatively: At this point, the screw described above can be replaced by a special screw as anti-theft pro- tection. » Device is installed. Proceed with the electrical installation. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 19 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 20
Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installation. › Immediately remove any moisture from the housing. Page 20 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
1 Slide the cable fitting over the cable. 2 Select seal according to cable diameter used. Page 22 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 23
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm in the “Parameters” menu Menu [See section 9.4.1} Page 36]. For questions regarding the appropriate type, please contact the installer or our KACO new energy cus- tomer service.
The threshold value from which the insulation monitor reports an error can be set in the “Parameters” menu. Page 24 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 30
The digital input of the device is intended for connection of a Powador-protect. When using devices from other manufacturers or in combination with KACO inverters, interface switches as a minimum must be used for shutting down devices from other manufacturers.
*) The waiting period ensures that the generator voltage continuously remains above the power delivery limit of 200 V. For country-specific waiting periods see our website. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 33...
Page 34
Opening a menu item or a setting F Use the right arrow button and the Enter button. Page 34 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
If no button is pressed for an adjustable period of time, the backlighting switches off again. You can also activ- ate or disable the backlighting permanently. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 35...
Displays the current value of the external power limitation by the grid operator. Page 36 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 39
F Set network port. Connection status Indicates the status of the network connection. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 39 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 40
2 Where applicable, set period from occurrence of the fault to shut- down of the device. Page 40 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 41
LC display, then the value of f is automatically set to the value of max. f>. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 41 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 42
4 Confirm the entry with the Enter button. Fault ride-through NOTE: The device doesn't support dynamic grid stabilization (Fault Ride-Through). Page 42 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 43
(per thousand) /minute (if mode "1" or mode "2" is active. This menu option is displayed permanently for IT and IL!). KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 43 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 44
1s – 120 s sponse corresponds to a first-order filter (PT-1) with settling time = 5Tau. Page 44 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 45
NOTE: Grid operators require shutdown of the device with standalone grid detection. F Further parameterisation is possible via the web interface. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 45 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 46
Priority – Reactive cur- F Select a control process. rent limitation | Active current priority Page 46 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 47
F Set min. and max. switch-on voltage after grid monitoring. after grid failure Max conn. voltage after grid failure KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 47 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 52
Regardless of the display data selected in the “Choose view” area, an export file always contains all meas- urement data and yield data available for the selected period. Page 52 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
3 When an error occurs, the update process must be repeated. You can check to see if the update was successful in the menu: KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 53...
(PT-1) with a time constant of Tau=200ms. The specified displacement factor may be configured in the display or via communication, via KACO RS485 protocol and MODBUS/SunSpec. If the applicable grid code requires the cos-φ response to set point by a defined gradient or settling time slower than the configured Tau=200ms, this gradient or settling time must be implemented in the plant control system.
Page 56
5 Tau. Lock-in voltage The control is activated above this voltage. 23V – 287V Page 56 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 59
In this case, P(U) control is available for making optimum use of the capacity of the upstream grid. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 59...
Page 61
52] [} Page 61]. The drop s can be transformed into a gradient g in accordance with equation 4 [See figure 53] [} Page 61]. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 61 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 62
Power reference for power adjustment as in equation 6 and equation 7 with underfrequency for overfrequency incidents. Actual power | Nominal power Page 62 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
If a reduction in power occurs, the power is brought back up to the pre-fault level within 100 ms of the voltage returning. Page 64 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 65
The pre-fault voltage is calculated as a 1-min mean value. Fig. 59: Formula no. 3 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 65 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Considering the fact that all KACO TL3 inverters have a semi-circular P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power be- cause an apparent power reserve is not available.
Page 69
In the event of active stage 1, the device switches to zero current mode, and re- starts the infeed after a few 100ms. At stage 2, the device has shut down and the set reconnection conditions apply. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 69...
1 Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top of the device on a regular basis. Page 70 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. › If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH Service. ›...
B = Operator’s responsibility ; E = The indicated work may only be carried out by an authorised electrician. ; K = The indic- ated work may only be carried out by a service employee of KACO new energy GmbH! 11.7...
Page 76
Grid frequency below the minimum permiss- Notify your author- ible grid frequency set ised electrician. Page 76 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 77
See description in the event of a fault 82 In case of repeated volt. L2 occurrence: Notify your authorised electrician. KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blue- Page 77 planet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Page 80
If fault numbers are displayed on the device but are not listed here, then it is usually necessary to have this looked at by your installation partner. Page 80 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
F Store the device at a dry location, in accordance with the ambient temperature range Environmental data [See sec- tion 4.3} Page 14]. Page 82 KACO blueplanet 3.0TL3 KACO blueplanet 4.0TL3 KACO blueplanet 5.0TL3 KACO blueplanet 6.5TL3 KACO blueplanet 7.5 TL3 KACO blueplanet 8.6TL3 KACO blueplanet 9.0TL3 KACO blueplanet 10.0TL3...
Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: Device name / serial number ...
Unauthorised modifications to the supplied devices and/or any use of the devices that is contrary to their intended use render this Declaration of Conformity null and void. This declaration of conformity is issued under the sole responsibility of KACO new energy GmbH. Neckarsulm, 05/27/2020...