H4: Analog Outputs

H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
Calibrate Meters Connected to MFAO Terminal AM
Use these parameters to calibrate meters connected to terminal AM:
• H4-02 [Terminal AM Analog Output Gain]
• H4-03 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and parameter H4-07 [Terminal AM Signal Level Select] to set the voltage output and current
output.
No.
H4-02
Terminal AM Analog Output Gain
H4-03
Terminal AM Analog Output Bias
H4-07
Terminal AM Signal Level Select
Figure 2.94
and
Figure 2.95
For example, when the parameter value set to analog output is 0, and a 3 V signal is to be output to terminal AM, set
H4-03 [AM Analog Output Bias] = 30%.
YASKAWA TOEPYAIGA5002A GA500 Programming
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Name
show the gain and bias.
Figure 2.94 Analog Output Gain/Bias Configuration Example 1
2.8 H: Terminal Function Selection
Description
Description
Range
-999.9 - +999.9%
100.0%
-999.9 - +999.9%
0.0%
0: 0 +10 VDC
0
2: 4-20 mA
Default
2
343