H4: Analog Outputs
H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
■
Calibrate Meters Connected to MFAO Terminal AM
Use these parameters to calibrate meters connected to terminal AM:
• H4-02 [Terminal AM Analog Output Gain]
• H4-03 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and parameter H4-07 [Terminal AM Signal Level Select] to set the voltage output and current
output.
No.
H4-02
Terminal AM Analog Output Gain
H4-03
Terminal AM Analog Output Bias
H4-07
Terminal AM Signal Level Select
Figure 2.94
and
Figure 2.95
For example, when the parameter value set to analog output is 0, and a 3 V signal is to be output to terminal AM, set
H4-03 [AM Analog Output Bias] = 30%.