1.21 Defaults by Drive Model and Duty Rating ND/HD
*1
No.
-
C6-01
o2-04
E2-11
(E4-11, E5-02)
b3-04
V/f Gain during Speed Search
b3-06
Speed Estimation Current Level 1
b3-08
Speed Estimation ACR P Gain
b3-26
Direction Determination Level
b8-03
Energy Saving Filter Time
b8-04
Energy Saving Coefficient Value
C6-02
Carrier Frequency Selection
E2-01
Motor Rated Current (FLA)
(E4-01)
E2-02
Motor Rated Slip
(E4-02)
E2-03
Motor No-Load Current
(E4-03)
E2-05
Motor Line-to-Line Resistance
(E4-05)
E2-06
Motor Leakage Inductance
(E4-06)
E2-10
Motor Iron Loss
(E4-10)
E5-01
PM Motor Code Selection
L2-02
Power Loss Ride Through Time
L2-03
Minimum Baseblock Time
Powerloss V/f Recovery Ramp
L2-04
Time
L2-05
Undervoltage Detection Lvl (Uv1)
L3-02
Stall Prevent Level during Accel
L3-06
Stall Prevent Level during Run
L3-24
Motor Accel Time @ Rated Torque
L8-02
Overheat Alarm Level
L8-09
Output Ground Fault Detection
n1-03
Hunting Prevention Time Constant
HSB Current Limit Level
n3-02
n5-02
Motor Inertia Acceleration Time
*1
Parameters within parentheses are for motor 2.
126
Name
Drive Model
Normal / Heavy Duty
Selection
Drive Model (KVA) Selection
Motor Rated Power
Unit
-
HD
-
Hex.
kW
22
%
100
-
0.5
-
0.5
-
1000
s
0.5
-
103.58
-
A
38.6
Hz
1.7
A
9.2
Ω
0.316
%
23.5
W
586
-
FFFF
s
s
s
0.6
-
380
%
150
%
150
s
0.355
°C
115
-
ms
10
%
150
s
0.355
YASKAWA TOEPYAIGA5002A GA500 Programming
Default
4060
ND
0
1
9F
30
100
0.5
0.5
1000
0.5
92.54
3
7
52.3
1.8
10.9
0.269
20.7
750
FFFF
2
2
1
1.1
0.6
380
120
120
0.323
115
1
1
10
120
0.323

Hide quick links: