YASKAWA GA500 Series Programming page 76

Industrial ac microdrive
Table of Contents

Advertisement

1.11 L: Protection Functions
No.
Name
(Hex.)
L8-35
Installation Method
Selection
(04EC)
L8-40
Carrier Freq Reduction
Off-Delay
(04F1)
L8-41
High Current Alarm
Selection
(04F2)
L8-51
STPo I Detection Level
(0471)
Expert
L8-52
STPo Integration Level
(0472)
Expert
L8-53
STPo Integration Time
(0473)
Expert
L8-54
STPo Id Diff Detection
(0474)
Expert
L8-55
Internal DB
TransistorProtection
(045F)
L8-56
Stall P @ Accel
Activation Time
(047D)
Expert
L8-57
Stall Prevention Retry
Counts
(047E)
Expert
L8-90
STPo Detection Level
(Low Speed)
(0175)
Expert
L8-93
Low Speed Pull-out
DetectionTime
(073C)
Expert
L8-94
Low Speed Pull-out
Detect Level
(073D)
Expert
L8-95
Low Speed Pull-out
Amount
(077F)
Expert
76
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the type of drive installation.
0 : IP20/UL Open Type
1 : Side-by-Side Mounting
2 : IP20/UL Type 1
3 : External Heatsink
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time until the automatically reduced carrier frequency returns to the
condition before the reduction.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to cause an HCA [Current Alarm] when the output current is more than
150% of the drive rated current.
0 : No
1 : Yes
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the STPo [Motor Step-Out Detected] detection level as a percentage of the motor
rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5 [OLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the detection level for STPo [Motor Step-Out Detected] related to the ACR integral
value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time until the drive detects STPo after it is more than the value of L8-51
[STPo I Detection Level].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Id deviation detection function for STPo [Motor Step-Out Detected].
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the protection function for the internal braking transistor.
0 : Disable
1 : Protection Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length time that the acceleration stall prevention function can continue to operate
before the drive detects an STPo [Motor Step-Out Detected].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the number of times the acceleration stall prevention function can operate until speeds
agree before the drive detects an STPo [Motor Step-Out Detected].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the detection level that the control fault must be equal to or more than to cause an
STPo [Motor Step-Out Detected].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time the drive will wait to start baseblock after detecting LSo [Low
Speed Motor Step-Out].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the detection level for LSo [Low Speed Motor Step-Out] as a percentage of E1-04
[Maximum Output Frequency].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the average count of LSo [Low Speed Motor Step-Out] detections.
Description
YASKAWA TOEPYAIGA5002A GA500 Programming
Default
Ref.
(Range)
0
401
(0 - 3)
Determined by A1-02
402
(0.00 - 2.00 s)
0
402
(0, 1)
0.0%
402
(0.0 - 300.0%)
1.0
403
(0.1 - 2.0)
1.0 s
403
(1.0 - 10.0 s)
1
403
(0, 1)
1
403
(0, 1)
5000 ms
403
(100 - 5000 ms)
10
404
(1 - 10 times)
Determined by A1-02
404
(0 - 5000 times)
1.0 s
404
(0.0 - 10.0 s)
3%
404
(0 - 10%)
10
404
(1 - 50 times)