Installation and Wiring

6.1 Installation

Please follow the installation instructions carefully to prevent failure or malfunctions.

6.1.1 Installation Environment and Space

Operating environment
After installing the unit, make sure to use it within the range of the general specifications:
Ambient temperature: 0–+55°C
Ambient humidity: 10%–95% RH (at 25°C non-condensing)
Pollution level: 2
Do not use the unit in the following environments:
Direct sunlight
-
Sudden temperature changes causing condensation
-
Inflammable or corrosive gases
-
Excessive airborne dust, metal particles or salts
-
Benzine, paint thinner, alcohol or other organic solvents or strong alkaline
-
solutions such as ammonia or caustic soda
Direct vibration, shock or direct drop of water
-
Influence from power transmission lines, high voltage equipment, power cables,
-
power equipment, radio transmitters, or any other equipment that would generate
high switching surges. Maintain at least 100mm of space between these devices
and the unit.
Static electricity
Before touching the unit or equipment, always touch some grounded metal to
discharge any static electricity you may have generated (especially in dry locations).
The discharge of static electricity can damage parts and equipment.
Measures regarding heat discharge
Always install the CPU orientated with the TOOL port facing outward on the bottom in
order to prevent the generation of heat.
68