9.2 Security Settings in FPWIN Pro

In FPWIN Pro, Online  Security Settings opens a dialog that displays the current security
settings and enables you to protect your PLC.
The LEDs in the dialog display the PLC's current protection status. To display a tool tip, hold
the cursor over the LED for approximately 2s.
REFERENCE
For a detailed description of the options in the Security Settings dialog box,
please refer to the FPWIN Pro online help.

9.2.1 Upload Protection

When upload protection is enabled, you cannot:
upload projects or program code to a PC
upload system registers to a PC
Data can be lost permanently - even if you know the password!
When using this function, be sure to back up your programs! The
!
program on your PLC will not be recoverable, either by a person knowing
the password or by customer support.
You can cancel the setting for this function using FPWIN Pro. However, all programs, system
registers and password information will be deleted!
If upload protection is enabled, you can edit files on the PLC while online using FPWIN Pro.
However, programs will be corrupted if the program in FPWIN Pro and the program on the
PLC are not identical.
NOTE
Even if upload protection has been set, upload to the FP Memory Loader is
possible. If you are using FP Memory Loader version 2 or higher, you can
enable or disable program upload to the FP Memory Loader or program transfer
between two PLCs using the FP Memory Loader. For details, see "FP Memory
Loader" on page 223.