7.7.2 Link Area Allocation

To use the PLC link function, link areas need to be allocated. Set the allocations for both the
link relays and link registers using the system registers of the CPU.
Link areas consist of link relays and link registers and are divided into areas for PLC link 0
and PLC link 1. A maximum of 1024 link relays (points) and 128 link registers (words) can be
used in the PLC link areas.
Link relays
0
63
64
127
Unit: words
1
For PLC link 0: 1024 points (1st half)
2
For PLC link 1: 1024 points (2nd half)
System registers
No.
Name
46
PLC Link 0 and 1 allocation setting
Link relays - Send/receive area - Number of words shared by all
40
linked PLCs
Link registers - Send/receive area - Number of words shared by
41
all linked PLCs
PLC link
42
Link relays - Send area - Start sending from this word address
0
43
Link relays - Send area - Number of words to send
44
Link registers - Send area - Start sending from this word address
45
Link registers - Send area - Number of words to send
1)
47
Highest station number in network
Link relays - Send/receive area - Number of words shared by all
50
linked PLCs
Link registers - Send/receive area - Number of words shared by
51
all linked PLCs
PLC link
52
Link relays - Send area - Start sending from this word address
1
53
Link relays - Send area - Number of words to send
54
Link registers - Send area - Start sending from this word address
55
Link registers - Send area - Number of words to send
1)
57
Highest station number in network
154
Link registers
0
127
128
255
1
For PLC link 0: 128 words (1st half)
2
For PLC link 1: 128 words (2nd half)
Default
Set values
value
Normal: 1st half
Normal
Reverse: 2nd
half
0
0-64 words
0
0-128 words
0
0-63
0
0-64 words
0
0-127
0
0-128 words
16
1-16
0
0-64 words
0
0-128 words
64
64-127
0
0-64 words
128
128-255
0
0-128 words
0
0-16