Panasonic FP0R User Manual page 171

Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

Communication
Reception done judgment time
The process for receiving a message is complete after all data has been received and the
time given in this table has been reached.
Baud rate
2400
4800
9600
19200
38400
57600
115200
Supported commands
Executable instructions for
master
F146_READ
F146_READ
F146_READ
F146_READ
F145_WRITE
F145_WRITE
Cannot be issued
F145_WRITE
F145_WRITE
Cannot be issued
Cannot be issued
Modbus references and FP0R addresses
Modbus reference
Name
Coil
Input
C10, C14, C16
Holding register
C32, T32, F32
Input register
1)
Beginning with 0
170
Reception done judgment time
Code
Name (Modbus
(decimal)
original)
01
Read Coil Status
02
Read Input Status
Read Holding
03
Registers
04
Read Input Registers
05
Force Single Coil
06
Preset Single Register Write DT 1 Word
08
Diagnostics
15
Force Multiple Coils
Preset Multiple
16
Registers
Mask Write 4X
22
Register
Read/Write 4X
23
Registers
Decimal address
000001–001760
002049–006144
100001–001760
400001–412315
40001–432765
300001–300128
302001–302256
13.3ms
6.7ms
3.3ms
1.7ms
0.8ms
0.6ms
0.3ms
Name for FP0R
Read Y and R Coils
Read X Input
Read DT
Read WL and LD
Write Single Y and R
Loopback Test
Write Multiple Ys and
Rs
Write DT Multiple
Words
Write DT Mask
Read/Write DT
1)
Hexadecimal address
0000–06DF
0800–17FF
0000–06DF
0000–301B
0000–7FFC
0000–007F
07D0–08CF
2)
Beginning with 1
Modbus
Reference
0X
1X
4X
3X
0X
4X
0X
4X
4X
4X
PLC address
2)
Y0–Y109F
R0–R255F
X0–X109F
DT0–DT12314
DT0–DT32764
WL0–WL127
LD0–LD255