Setting Communication Conditions

4.1 Settings Using FPWIN GR7

 Set the "Communication Mode", "Station no." and others in the FPWIN GR7.
 These configuration will downloaded to the PLC with Programs as a Project.
PROCEDURE
1.
Select "Options" > "FP7 Configuration" from the menu bar,
The "FP7 Configuration" dialog box opens.
2. Select "Built-in SCU".
Setting items for "Built-in SCU" appear.
3. Press [OK], after setting for communication conditions of COM.1 port.
Set conditions are incorporated into the project that is being edited.
KEY POINTS
Select the "Built-in SCU" for the Communication cassette AFP7CCET1 to
recognised as serial communication in the internal system.
Settings for the COM.2 ports is not available for the Communication
cassette AFP7CCET1.