Battery Control; Figure 13 Internal, External Battery Cable Connection With Units - Emerson Liebert NX User Manual

10-20, 400v, 50/60hz, 3x1
Hide thumbs Also See for Liebert NX:
Table of Contents

Advertisement

Battery Installation
2.5

Battery Control

Battery temperature sensor cables are connected between UPS auxiliary terminal block X3 BCB, the
Battery Temperature sensor and the battery as shown in Figure 7.
Cables connected to X3 BCB must contain a protective earth wire or a shield, be segregated from
power circuits, double insulated and of a typical 0.5 to 1mm2 cross section area for maximum runs
between 25 and 50 meters respectively. The shield should be connected to the protective earth of the
battery cabinet or battery breaker, not at the UPS.

Figure 13 Internal, external battery cable connection with units

Internal Battery Terminal
Fuse
External Battery Terminal
24
Fuse