SDD ES ETH
Setting the IP address via the web server
For details of how to set the IP address via the implemented web server, refer to the sec-
tion entitled
If a fixed IP address has been assigned via the web server, then this will be used.

Operation

The SDD ES ETH is ready for operation when the "Power" LED is lit and the "Fault" LED is
unlit.
Legend
LED
Power
ModbusTCP
Devices
Start up
Fault
Operating Manual SDD ES ETH
1003824-EN-06
Web server [
23].
LED on
LED flashes
LED off
State
Green
Green
Green
Yellow
Red
Meaning / action
Supply voltage is outside the permitted range
(see
Technical details [
Supply voltage is present
No access via the bus connection
Access via the bus connection
All connected devices are enabled
At least one connected device is not enabled
Normal operation
Device data is being polled
Normal operation
Fault on the SDD ES ETH.
Check the supply voltage, wiring and configura-
tion of the SDD ES ETH.
The system continues to attempt to poll the con-
nected sensors and to create a full list of the con-
nected sensors. In the web interface, therefore,
the status in Device Info alternately displays
"Initializing" and a yellow status bar, or "Error
Handling" and a red status bar.
Internal fault on the SDD ES ETH
Remedy: Replace the device
32])