PSS SB DI16 Contents Introduction Validity of the documentation Overview Intended use System requirements CPU versions System software versions Functions Inputs Detecting signals at the inputs Signal change behaviour Test pulse outputs/24 VDC terminals Schematic internal wiring diagram Operation of the module on SafetyBUS p...
Each test pulse output has 4 terminals, which can also be configured in pairs as 24 VDC terminals. The PSS SB DI16 requires a 24 V supply, which feeds both the module electronics and the dedicated test pulse outputs. The module is galvanically isolated from SafetyBUS p via optocouplers.
This means that all safety systems with Logic Device functionality which are assigned to I/O-Group(s) on the PSS SB DI16, and the safety system with Manage- ment Device functionality, must all support the module.
Test pulses must be used for applications with single-channel input devices above category 2 and applications with dual-channel input devices above category 3. Connection diagrams can be found in the “PSS SB DI16 Installation Manual”. Inputs can be allocated to two I/O-Groups. For further information please refer to “Operation of the module on SafetyBUS p”.
PSS SB DI16 The presence of a signal (“0” or “1” signal) will be ignored if it does not exceed the pulse suppression time of 300 µs. In this case, no Event Telegram will be sent. : Pulse length for guaranteed signal detection for “1” or “0” signals (>...
Each terminal pair has a maximum load capacity of 0.5 A, irrespective of its use. Schematic internal wiring diagram The diagram on page 8 shows a schematic internal wiring diagram of the PSS SB DI16, showing galvanic isolation from SafetyBUS p, etc. Operating Manual...
Page 10
/ 24 V DC / 24 V DC 24 V DC / 24 V DC Ground (2-channel) 6,6 nF Ground 2,4 M 3,3 nF Ground Supply Supply 24 V Fig. 3: Schematic internal wiring diagram of the PSS SB DI16 Operating Manual...
Operation of the module on SafetyBUS p The module is connected to SafetyBUS p via a male 9-pin D-Sub connector. Fibre-optic couplers from Pilz (like PSS SB SUB-D F0) can be connected to the SafetyBUS p interface. To enable the module to operate on SafetyBUS p, it must be given the device address set via the configurator in the system software.
PSS SB DI16 Display elements LEDs for status display Each input is assigned an LED for status display. If the input is high, the corresponding LED will light. If it goes low, the LED will go out. LED “Supply” Indicates that the supply is present.
Recommended free space for wiring Fig. 4: Installing the PSS SB DI16, dimensions stated in mm (") Dimensions in mm ("): H x W x D: 140 x 170 x 65 (5.51 x 6.69 x 2.56) The module can be attached to a 35 mm DIN-rail (top hat rail) or can be screwed on to mounting plate using fixing bolts (order no.
PSS SB DI16 Commissioning General guidelines are given below, but you should always refer to the “PSS SB DI16 Installation Manual” (this is part of the “Safety BUS p” System Manual and is also enclosed with every Safety BUS p-compatible PSS): •...
Module configuration The procedure for configuring SafetyBUS p and the PSS SB DI16 module is described in the online help of the PSS WIN-PRO system software. Operating Manual...
PSS SB DI16 Technical details Electrical data Supply voltage 24 V DC Tolerance 20 ... 30 V DC including residual ripple of max. ± 1.2 V Power consumtion "Supply": 90 mA plus load currents from the test pulse outputs and load currents for fibre-optic couplers (25 mA per fibre- optic coupler);...
Page 17
ENGLISH Environmental data Protection type (EN 60529) IP20 Mounting position Ambient temperature (EN 60068-2-14) 0 ... 60 °C Storage temp. (EN 60068-2-1/-2) -25 ... +70 °C Climatic suitability (EN 60068-2-78) Max. 95 % r. h. Condensation Not permitted Vibration (EN 60068-2-6) Frequency range: 10 ...
PSS SB DI16 Changes in the documentation Changes from version I to version II Change p. no. p. no. Internal wiring diagram was amended. Changes from version II to version III Change p. no. p. no. New: section “Detecting signals at the inputs”...
Page 19
Changes from version VI to version V Change p. no. p. no. Pulse suppression now 300 µs Pulse suppression now 300 µs New: Pulse suppression in Technical details Changes in version 20 085-07 Change p. no. p. no. Norms updated New: section "System software versions"...
Page 21
In many countries we are www.pilz.com represented by sales partners. Please refer to our Homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Sichere Automation Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de...