High Pressure Sensor; Comparing The High Pressure Sensor Measurement And Gauge Pressure; High Pressure Sensor Configuration (63Hs) - Mitsubishi Electric PUMY-P250YBM Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

<HIGH PRESSURE SENSOR>

• Comparing the High Pressure Sensor Measurement and Gauge Pressure

By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the high
pressure sensor appears on the LED1 on the control board.
ON
The figure at left shows that the switches 1 through 4 are set to ON and 5 through 8 are set to OFF.
2
3
4
5
6
7
8
1
(1) While the outdoor unit is stopped, compare the gauge pressure and the pressure displayed on self-diagnosis
LED1, 2.
1) When the gauge pressure is between 0 and 0.098 MPaG [14 PSIG], internal pressure is caused due to gas leak.
2) When the pressure displayed on self-diagnosis LED1, 2 is between 0 and 0.098 MPaG [14 PSIG], the connector may be
defective or be disconnected. Check the connector and go to (4).
3) When the pressure displayed on self-diagnosis LED1, 2 exceeds 5.0 MPaG [725 PSIG], go to (3).
4) If other than 1), 2) or 3), compare the pressures while the sensor is running. Go to (2).
(2) Compare the gauge pressure and the pressure displayed on self-diagnosis LED1,2 after 15 minutes have passed
since the start of operation. (Compare them by MPaG [PSIG] unit.)
1) When the difference between both pressures is within 0.25 MPaG [36 PSIG], both the high pressure sensor and the con-
trol board are normal.
2) When the difference between both pressures exceeds 0.25 MPaG [36 PSIG], the high pressure sensor has a problem.
(performance deterioration)
3) When the pressure displayed on self-diagnosis LED1, 2 does not change, the high pressure sensor has a problem.
(3) Remove the high pressure sensor from the control board to check the pressure on the self-diagnosis LED1, 2.
1) When the pressure displayed on self-diagnosis LED1, 2 is between 0 and 0.098 MPaG [14 PSIG], the high pressure sen-
sor has a problem.
2) When the pressure displayed on self-diagnosis LED1, 2 is approximately 5.0 MPaG [725 PSIG], the control board has a
problem.
(4) Remove the high pressure sensor from the control board, and short-circuit between the pin 2 and pin 3 connectors
(63HS) to check the pressure with self-diagnosis LED1, 2.
1) When the pressure displayed on the self-diagnosis LED1, 2 exceeds 5.0 MPaG [725 PSIG], the high pressure sensor has
a problem.
2) If other than 1), the control board has a problem.

• High Pressure Sensor Configuration (63HS)

The high pressure sensor consists of the circuit shown in the figure below. If 5 VDC is applied between the red and the black
wires, voltage corresponding to the pressure between the white and the black wires will be output, and the value of this volt-
age will be converted by the microprocessor. The output voltage is 0.078 V per 0.098 MPaG [14 PSIG].
Note: The pressure sensor on the body side is designed to connect to the connector. The connector pin number on the body
side is different from that on the control board side.
Body side
Vcc
Vout
GND
OUTDOOR MULTI CONTROLLER
CIRCUIT BOARD
5 VDC
3
RD
2
WH
MICRO
Vout
PROCESSOR
1
BK
GND
63HS
3–1: 5 V(DC)
2–1: Output Vout (DC)
OCH760
SW1
ON
1
2
Control board side
Pin 1
Pin 3
Pin 2
Pin 2
Pin 3
Pin 1
Pressure: 0–5.0 MPaG [725 PSIG]
Vout: 0.5–4.5 V
0.078 V/0.098 MPaG [14 PSIG]
3
4
5
6
7
8
Vout (V)
100
4.5
2.5
0.5
0
2.5
5
363
725
PRESSURE
(MPaG)
(PSIG)