Mitsubishi Electric PUMY-P250YBM Technical & Service Manual page 44

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

Check code
1102
(U2)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Continued from the previous page.
Disconnect the thermistor wiring to check
the resistance.
Is the resistance detected?
Check the voltage and appearance of the
outdoor multi controller circuit board.
Is the voltage normal value?
Is it free from any trace of over-
heating or burning?
Disconnect the indoor LEV wiring and
check the resistance.
Is the resistance detected?
OCH760
Compressor temperature trouble
Diagnosis
Yes
Yes
Yes
No
Replace the outdoor multi controller circuit
No
board.
No
Replace the indoor controller board.
44
Chart 2 of 2
Remedy
Replace the thermistor.
Replace the indoor LEV.