8-1-3. Countermeasures for Error During Test Run

• If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and the
air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
Check
Check
code
code
(2 digits)
(4 digits)
Ed
0403
Serial communication error
U2
1102
Compressor temperature trouble
UE
1302
High pressure trouble
U7
1500
Superheat due to low discharge temperature trouble
Refrigerant shortage trouble
U2
1501
Closed valve in cooling mode
P6
1503
Freeze protection of Branch box or Indoor unit
EF
1508
4-way valve trouble in heating mode
PA
2500
Water leakage
P5
2502
Drain overflow protection
P4
2503
Drain sensor trouble
UF
4100
Compressor current interruption (locked compressor)
Pb
4114
Fan trouble (indoor)
Compressor overcurrent interruption/failure in 12 VDC power
UP
4210
supply circuit on power circuit board
Undervoltage/overvoltage/PAM error/L1 open phase/power
U9
4220
synchronization signal error
U5
4230
Heat sink temperature trouble
U6
4250
Power module trouble or overcurrent trouble
U8
4400
Fan trouble (outdoor)
Air inlet thermistor (TH21) open/short or
U3
5101
Compressor temperature thermistor (TH4) open/short
Liquid pipe temperature thermistor (TH22) open/short or
U4
5102
Suction pipe temperature thermistor (TH6) open/short
U4
5103
Gas pipe temperature thermistor (TH23) open/short
U4
5105
Outdoor liquid pipe temperature thermistor (TH3) open/short
U4
5106
Ambient thermistor (TH7) open/short
U4
5109
HIC pipe temperature thermistor (TH2) open/short
U4
5110
Heat sink temperature thermistor (TH8) open/short
F5
5201
High pressure sensor (63HS) trouble
F3
5202
Low pressure sensor (63LS) trouble
UH
5300
Current sensor trouble
P4
5701
Contact failure of drain float switch
A0
6600
Duplex address error
A2
6602
Transmission processor hardware error
A3
6603
Transmission bus BUSY error
A6
6606
Signal communication error with transmission processor
A7
6607
No ACK error
A8
6608
No response frame error
E0/E4
6831
MA communication receive error (no receive signal)
E3/E5
6832
MA communication send error
E3/E5
6833
MA communication send error
E0/E4
6834
MA communication receive error
EF
7100
Total capacity error
EF
7101
Capacity code error
EF
7102
Connecting unit number error
Address setting error
EF
7105
Incompatible unit combination
EF
7130
Notes:
1. When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
2. Refer to the service manual of indoor unit or remote controller for the detail of error detected in indoor unit or remote controller.

Self-diagnosis function

The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1, SWP2) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Bit
1
2
Compressor
Indication
52C
operated
OCH760
Trouble
3
4
5
6
21S4
SV1
(SV2)
SV3
Detected Unit
Remote
Indoor
Outdoor
Controller
7
8
Always lit
41
Remarks
Outdoor unit outdoor multi controller circuit board
– Power circuit board communication trouble
Check delay code 1202
Check delay code 1402
Check delay code 1600
Check delay code 1601
Check delay code 1501
Check delay code 1608
Check delay code 4350
Check delay code 4320
Check delay code 4330
Check delay code 4350
Check delay code 4500
Check delay code 1202
Check delay code 1211
Check delay code 1205
Check delay code 1221
Check delay code 1222
Check delay code 1214
Check delay code 1402
Check delay code 1400
Check delay code 4310
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
[Example]
When the compressor and
SV1 are turned during cooling
operation.
1 2 3 4 5 6 7 8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents