Heating Calculation; Temporary Selection Of Indoor Units; Total Indoor Units Capacity; Selection Of Outdoor Unit - Mitsubishi Electric PUMY-P250YBM Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

<Heating>
Outdoor Design Wet Bulb Temperature
Total Heating Load
Room1, Room2
Indoor Design Dry Bulb Temperature
Heating Load
Room3, Room4
Indoor Design Dry Bulb Temperature
Heating Load
<Other>
Indoor/Outdoor Equivalent Piping Length
Capacity of indoor unit
P•FY Series Model Number for
indoor unit
Model
Capacity
M Series
Model Number for
indoor unit
Model
Capacity

2. Heating Calculation

(1) Temporary Selection of Indoor Units

Room1, Room2
PEFY-P63
Room3, Room4
PEFY-P71

(2) Total Indoor Units Capacity

P63 + P63 + P71 + P71 = P268

(3) Selection of Outdoor Unit

The P300 outdoor unit is selected as total indoor units capacity is P268
PUMY-P300YBM
(4) Total Indoor Units Capacity Correction Calculation
Room1, Room2
Indoor Design Dry Bulb Temperature Correction (24ºC)
Room3, Room4
Indoor Design Dry Bulb Temperature Correction (25ºC)
Total Indoor Units Capacity (CTi)
CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction)
= 8.0×0.84 + 8.0×0.84 + 9.0×0.80 + 9.0×0.80
= 27.8 kW
(5) Outdoor Unit Correction Calculation
Outdoor Design Wet Bulb Temperature Correction (2ºC)
Piping Length Correction (30 m)
Defrost Correction
Total Outdoor Unit Capacity (CTo))
CTo = Outdoor Unit Rating × Outdoor Design Temperature Correction × Piping Length
Correction × Defrost Correction
= 37.5 × 1.00 × 0.98 × 0.89
= 32.7 kW
(6) Determination of Maximum System Capacity
Comparison of Capacity between Total Indoor Units Capacity (CTi) and Total Outdoor Unit Capacity (CTo)
CTi = 27.8 < CTo = 32.7, thus, select CTi.
CTx = CTi = 27.8 kW
(7) Comparison with Essential Load
Against the essential load 25.0kW, the maximum system capacity is 27.8 kW: Proper outdoor units have been selected.
(8) Calculation of Maximum Indoor Unit Capacity of Each Room
CTx = CTi, thus, calculate by the calculation below
Room1, 2
Indoor Unit Rating × Indoor Design Temperature Correction
= 8.0 × 0.84
= 6.7 kW
Room3, 4
Indoor Unit Rating × Indoor Design Temperature Correction
= 9.0 × 0.80
= 7.2 kW
Note: If CTx = CTo, please refer to the <Cooling> section to calculate the Maximum Indoor Unit Capacity of Each Room.
Completed selecting units since the selected units fulfill the heating loads of Room 1 to 4.
OCH760
Design Condition
Model
Model
Model
Model
Model
10
15
20
25
1.4
1.9
2.5
3.2
4.0
Model
Model
Model
Model
Model
15
18
20
22
1.7
2.1
2.3
2.5
2.9
8.0 kW (Rated)
9.0 kW (Rated)
37.5 kW
OK: fulfills the load 6.0 kW
OK: fulfills the load 6.5 kW
2ºC
25.0 kW
24ºC
6.0 kW
25ºC
6.5 kW
30 m
Model
Model
Model
Model
32
40
50
63
71
5.0
6.3
8.0
9.0
Model
Model
Model
25
35
42
50
4.0
4.8
5.7
0.84 (Refer to Figure 4)
0.80 (Refer to Figure 4)
1.00 (Refer to Figure 5)
0.98
(Refer to Figure 6)
0.89
(Refer to Table 1)
Table 1 Table of correction factor at frost and defrost
Outdoor Intake
Temperature (°C W.B.)
Correction factor
12
Model
Model
Model
Model
Model
80
100
125
140
200
10.0
12.5
16.0
18.0
25.0
1.2
1.1
1.0
0.9
0.8
0.7
0.6
15
16
17
18
19
20
21
22
Indoor Temperature [°C D.B.]
Figure 4 Indoor unit temperature correction
To be used to correct indoor unit only
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
-20
-15
-10
-5
0
Outdoor Temperature [°C W.B.]
Figure 5 Outdoor unit temperature correction
To be used to correct outdoor unit only
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
80
100
Piping equivalent length (m)
Figure 6 Correction of refrigerant piping length
6
4
2
0
-2
-4
-6
1.00 0.98 0.89 0.88 0.89 0.90 0.95 0.95 0.95 0.95 0.95
Unit: kW
Model
250
31.5
23
24
25
26
27
Indoor temperature
20°C D.B.
5
10
15
120
140
160
180
-8 -10 -15 -20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents