Compressor Current Interruption (Locked Compressor); 4100 - Mitsubishi Electric PUMY-P250YBM Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

Check code

Compressor current interruption (Locked compressor)

4100

(UF)
Abnormal points and detection methods
If overcurrent of compressor is detected within 30 seconds since the
compressor starts operating.
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Check the stop valve.
Is the stop valve (liquid/gas) fully
open?
Check the power supply voltage.
Is the power supply voltage normal?
Turn the power OFF to check for
looseness, disconnection or phases of the
compressor wiring.
Is it connected properly?
Check whether the model selection switch is
set correctly on the outdoor multi controller
circuit board or not.
Continue to the next page.
OCH760
Diagnosis
Yes
Yes
Yes
Causes and checkpoints
Closed stop valve
Decrease of power supply voltage
Looseness, disconnection or converse of compressor
wiring connection
Incorrect DIP-SW setting of model selection on the
outdoor controller board
Defective compressor
Defective outdoor power circuit board
Open the stop valve (liquid/gas) fully.
No
Ensure power supply from the facility.
No
Connect the wiring properly,
No
then turn the power back ON.
56
Chart 1 of 2
Remedy