Mitsubishi Electric PUMY-P200YKM Installation Manual

Mitsubishi Electric PUMY-P200YKM Installation Manual

Hide thumbs Also See for PUMY-P200YKM:

Advertisement

Air-Conditioners
PUMY-P200YKM

INSTALLATION MANUAL

For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing
the air-conditioner unit.
INSTALLATIONSHANDBUCH
Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung
und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.
MANUEL D'INSTALLATION
Avant d'installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d'installation de l'appareil
intérieur pour une utilisation sûre et correcte.
INSTALLATIEHANDLEIDIN
Lees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het
installeren van de airconditioner begint.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior
antes de instalar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente il presente manuale ed il manuale d'installazione dell'unità
interna prima di installare il condizionatore d'aria.
E
EIPI IO O H I N E KATA TA H
MANUAL DE INSTALA
Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade
interior antes de instalar o aparelho de ar condicionado.
INSTALLATIONSMANUAL
Læs af sikkerhedshensyn denne manual samt manualen til installation af indendørsenheden grundigt, før du
installerer klimaanlægget.
INSTALLATIONSMANUAL
Läs bruksanvisningen och inomhusenhetens installationshandbok noga innan luftkonditioneringen installeras
så att den används på ett säkert och korrekt sätt.
MONTA ELK TABI
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
O
PARA O INSTALADOR
TIL INSTALLATØREN
FÖR INSTALLATÖREN
For use with R410A
FOR INSTALLER
En ish
B
Deuts h D
Fr n
is F
Neder nds NL
Es
o E
It i no I
E
R
Portu u s P
D ns
DA
S ens
S
T r
e TR
RU

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PUMY-P200YKM

  • Page 1: Installation Manual

    Air-Conditioners PUMY-P200YKM For use with R410A INSTALLATION MANUAL FOR INSTALLER En ish For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH FÜR INSTALLATEURE Deuts h D Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.
  • Page 2: Table Of Contents

    Con r ation o parts attached In addition to this manual, the following parts are supplied with the outdoor unit. <PUMY-P200YKM> They are used for grounding the S terminals of transmission terminal blocks TB3, TB7. For details refer to “6. Electrical work”.
  • Page 3: Safety Precautions

    1 Sa et precautions 1 1 Be ore insta ation Caution hen insta ing the unit in a hospita or co unications o ce e prepared or Do not use the unit in an unusua en iron ent I the air conditioner is insta ed in areas e posed to stea o ati e oi inc uding achine oi...
  • Page 4 2 Insta ation ocation 2 1 Re rigerant pipe Refer to Fig. 4-1. 2 2 Choosing the outdoor unit insta ation ocation bors. indoor unit. late. fall is anticipated, special precautions such as raising the installation location or installing a hood on the air intake must be taken to prevent the snow from block- malfunction may result.
  • Page 5: Installation Location

    2 Installation location 2 4 Ventilation and ser ice space 2 4 2 hen installing ultiple outdoor units Leave 25 mm space or more between the units. 2 4 1 hen installing a single outdoor unit 1 Obstacles at rear only (Fig. 2-8) Minimum dimensions are as follows, except for Max., meaning Maximum dimen- 2 Obstacles at rear and above only (Fig.
  • Page 6: Installing The Outdoor Unit

    2 Installation location ind location installation wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. may result. The following shows two examples of precautions against strong winds. 1 Install an optional air guide if the unit is installed in a location where strong winds from a typhoon, etc.
  • Page 7 4 Installing the re rigerant piping (mm) A+B+C+D+a+b+c+d+e 150 m L = A+B+C+D+e 80 m A Liquid pipe B Gas pipe 30 m ø9.52 ø19.05 60 m 50 m (Outdoor lower H 40 m) ø12.7 ø19.05 15 m B, C, D (mm) C Total capacity of indoor units A Liquid pipe...
  • Page 8 4 Installing the re rigerant piping Re rigerant piping Fig 4-4 Remove the service panel D (three screws) and the front piping cover A (two screws) and rear piping cover B (two screws). 1 Perform refrigerant piping connections for the indoor/outdoor unit when the outdoor unit’s stop valve is completely closed.
  • Page 9: Caution

    4 Installing the re rigerant piping Precautions when using the charge al e Fig 4- Do not tighten the service port too much when installing it, otherwise, the valve core could be deformed and become loose, causing a gas leak. only.
  • Page 10 Electrical wor 2 Control o and connecting position o wiring <PUMY-P·YKM> 1. Connect the indoor unit transmission line to transmission terminal block (TB3), or L1 L2 L3 N connect the wiring between outdoor units or the wiring with the centralized control system to the centralized control terminal block (TB7).
  • Page 11 Electrical wor 1 M-NET Re ote controller and L and L 500 m (1.25 mm or more) and L and L and L and L 200 m (1.25 mm or more) 10 m (0.5 to 1.25 mm If the length exceeds 10 m, use a 1.25 mm shielded wire.
  • Page 12 Electrical wor Connect to Connection kit (PAC-LV11M) Indoor unit Type 1 Sample chart Type 2 Type 3 Connection kit (PAC-LV11M) 6000 Indoor unit PMFY-VBM, PLFY-VBM, PEFY-VMS1, PCFY-VKM, Type 4 19.8 PKFY-VHM, PKFY-VKM, PFFY-VKM, PLFY-VFM SAMPLE Type 5 PLFY-VCM Type 6 PKFY-VBM Type 7 PEFY-VMA...
  • Page 13: Test Run

    Test run 1 Be ore test run A ter co pleting installation and the wiring and piping o the indoor and outdoor units chec or re rigerant lea age looseness in the power suppl or control wiring wrong polarit and no disconnection o one phase in the up for four hours.
  • Page 14 ..............134 ................141 ..................136 ................ 141 ............138 ...............145 ..............138 R410A <PUMY-P200YKM> IEC EN 61000-3-12 PUMY-P200YKM IEC 61000-3-12 (*1) (*1) (*1) (MVA) PUMY-P200YKM R410A R410A HFC- (R410A) R410A Mitsu ishi Electric C1220...
  • Page 15 R410A R410A R410A C1220 138) R410A...
  • Page 16 ) (Fig 2-1) P15 P20 P25 P32 P40 P50 P63 P71 P80 P100 P125 P140 P200 1-2 ( Fig 2-1 PUMY-P200 1-12...
  • Page 17: Fig 2-12 Fig

    2 4 2 2 4 1 Fig 2-2 Fig 2-3 Fig 2-4 Fig 2-5 1500 Fig 2-6 Fig 2-7 Fig 2-8 1500 Fig 2-9 Fig 2-10 Fig 2-11 Fig 2-12 Fig 2-13 Fig 2-14...
  • Page 18 2 5 3 Fig 2-15 Fig 2-16 M10 (3/8") 1050 Fig 3-1 R410A R410A C1220 (R410A) 1 2 H 19 05...
  • Page 19 F 4- G 8- (Fig 4-2) Fig 4-1 Fig 4-2 15-50 63-140 14 - 18 34 - 42 34 - 42 68 - 82 68 - 82 100 - 120 100 - 120 Fig 4-3...
  • Page 20 (Fig 4-4) Fig 4-4 Fig 4-5 (1) 1 Fig 4-6 (2) 1 Fig 4-7...
  • Page 21 (Fig 4-8) Fig 4-8 + 45 × 50 × 1000 1000...
  • Page 22 <PUMY-P·YKM> (Fig 6-1) L1 L2 L3 N Fig 6-1 – M-NET (Fig 6-2) MA (Fig 6-3) 01 - 50 01 - 50 51 - 100 101 - 150 151 - 200 –...
  • Page 23 M-NET M-NET (51) (51) (01) (02) (05) (06) (01) (02) (05) (06) TB15 TB15 TB15 TB15 M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S...
  • Page 24 6000 0,01 60245 IEC57)
  • Page 25 500- 7 2 1 7 2 2 7 2 1 DIP- S 3-2 ( DIP- S 3-1 DIP- S 3-1 )
  • Page 26 MITSUBISHI ELECTRIC PUMY-P200YKM Bemærk: Serienummeret står på produktets fabriksskilt. Remarque : Le numéro de série de l’appareil se trouve sur la plaque du produit.
  • Page 27 English is original. The other languages versions are translation of the original. O idioma original é o inglês. As versões em outros idiomas são traduções do idioma original. CAUTION CUIDADO in burns or frostbite. tubagens não isoladas pode resultar em queimaduras ou ulcerações provocadas pelo frio. A ingestão de uma pilha pode causar obstrução das vias respiratórias e/ou envenenamento.
  • Page 28 This product is designed and intended for use in the residential, commercial and light-industrial environment. Importer: Mitsubishi Electric Europe B.V. French Branch German Branch Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany Belgian Branch Autobaan 2, 8210 Loppem, Belgium Irish Branch Italian Branch...

Table of Contents