1302 - Mitsubishi Electric PUMY-P250YBM Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

Check code

1302

(UE)
Abnormal points and detection methods
(1) High pressure abnormality (63H operation)
If 63H operates(*) during compressor operation. (* 4.15 MPa)
(2) High pressure abnormality (63HS detected)
1. If a pressure detected by 63HS is 4.31 MPa or more during
compressor operation.
2. If a pressure detected by 63HS is 4.14 MPa or more for 3 minutes
during compressor operation.
63H:
High pressure switch
63HS: High pressure sensor
LEV:
Linear expansion valve
SV1:
Solenoid valve
TH7:
Thermistor <Ambient>
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Is 5201 displayed when restarted?
Is the outdoor stop valve (liquid/
gas) fully open?
Does the outdoor fan rotate
during the operation?
Does the indoor fan rotate during
the operation?
Is the indoor unit short-cycled?
Continue to the next page.
OCH760
High pressure trouble
Diagnosis
(5201)
(1302)
No
Yes
Yes
Yes
(short-cycled)
(no short-cycle)
No
Causes and checkpoints
Defective operation of stop valve (not fully open)
Clogged or broken pipe
Malfunction or locked outdoor fan motor
Short-cycle of outdoor unit
Dirt of outdoor heat exchanger
Remote controller transmitting error caused by noise interference
Contact failure of the outdoor multi controller circuit board connector
Defective outdoor multi controller circuit board
Short-cycle of indoor unit
Decreased airflow, clogged filter, or dirt on indoor unit.
Malfunction or locked indoor fan motor
Decreased airflow caused by defective inspection
of outdoor temperature thermistor (It detects lower
temperature than actual temperature.)
Indoor LEV performance failure
Malfunction of fan driving circuit
SV1 performance failure
Defective high pressure sensor
Defective high pressure sensor input circuit on
outdoor multi controller circuit board
Refer to the diagnosis of check code 5201.
Yes
Open the stop valve (liquid/gas) fully.
No
Check the outdoor fan motor.
Refer to "How to check the parts" on the
No
outdoor unit service manual.
Check the indoor fan motor.
No
Refer to "How to check the parts" on the
indoor unit service manual.
Yes
45
Chart 1 of 4
Remedy
Resolve the short-cycle.