8-7. HOW TO CHECK THE COMPONENTS

<Thermistor feature chart>

Low temperature thermistors

• Thermistor <HIC Pipe> (TH2)
• Thermistor <Outdoor Liquid Pipe> (TH3)
• Thermistor <Suction Pipe> (TH6)
• Thermistor <Ambient> (TH7)
Thermistor R0 = 15 kΩ ± 3 %
B constant = 3480 ± 1 %
1
R
=15exp{3480(
t
273+t
273
0°C
15 kΩ
30°C
10°C
9.6 kΩ
40°C
20°C
6.3 kΩ
25°C
5.2 kΩ

Medium temperature thermistor

• Thermistor <Heat Sink> (TH8)
Thermistor R50 = 17 kΩ ± 2 %
B constant = 4150 ± 3 %
1
R
=17exp{4150(
t
273+t
0°C
180 kΩ
25°C
50 kΩ
50°C
17 kΩ
70°C
8 kΩ
90°C
4 kΩ
High temperature thermistor
• Thermistor <Compressor> (TH4)
Thermistor R120 = 7.465 kΩ ± 2 %
B constant = 4057 ± 2 %
1
R
=7.465exp{4057(
t
273+t
20°C
250 kΩ
70°C
30°C
160 kΩ
80°C
40°C
104 kΩ
90°C
50°C
70 kΩ
100°C
60°C
48 kΩ
110°C
OCH760
1
)}
4.3 kΩ
3.0 kΩ
1
)}
323
1
)}
393
34 kΩ
24 kΩ
17.5 kΩ
13.0 kΩ
9.8 kΩ
50
40
30
20
10
0
-20 -10 0 10 20 30 40 50
200
150
100
50
0
500
400
300
200
100
0
99
Temperature (°C)
25
50
75
100 110 125
(°C)
Temperature
50
75
100
25
Temperature (°C)
120