Permissible Lengths
Longest transmission cable length:
L
+ L
[ 200 m (1.25 mm²)
1
2
MA remote controller cable length:
, R
[ 200 m (0.3 to 1.25 mm²)
R
1
2
Longest transmission cable length:
L
+ L
[ 200 m (1.25 mm²)
1
2
MA remote controller cable length:
+R
, R
[ 200 m
R
3
4
5
(0.3 to 1.25 mm²)
Longest transmission cable length:
L
+ L
[ 200 m (1.25 mm²)
1
2
MA remote controller cable length:
+R
[ 200 m (0.3 to 1.25 mm²)
R
6
7
OCH760
The MA remote controller and the M-NET remote controller cannot be used together with
the CITY MULTI series indoor unit of the same group.
M-NET remote controller cannot be connected without address setting.
OC
(00)
TB3
TB7
M1 M2 S
M1 M2 S
NO
A B
(00)
M-NET RC
3 MA remote controllers or more cannot be connected with the CITY MULTI series
indoor unit of the same group.
OC
(00)
TB3
TB7
M1 M2 S
M1 M2 S
NO
The second MA remote controller is connected with the terminal block (TB15) for the
MA remote controller of the same CITY MULTI series indoor unit (M-IC) as the first MA
remote control.
OC
(00)
TB3
TB7
M1 M2
S
M1 M2 S
33
Constraint items
M-IC
(00)
TB5
TB15
1 2
M1 M2 S
A B
MA-RC
M-IC
(00)
TB5
TB15
1 2
M1 M2 S
M1 M2 S
A B
A B
A B
MA-RC
MA-RC
MA-RC
(Main)
(Main)
(Sub)
M-IC
(00)
TB5
TB15
TB5
1 2
M1 M2 S
M1 M2 S
A B
MA-RC
M-IC
(00)
TB5
TB15
1 2
M1 M2 S
A B
MA-RC
M-IC
(00)
TB5
TB15
1 2
A B
A B
MA-RC
MA-RC
(Main)
(Sub)
M-IC
(00)
TB15
1 2
NO
A B
MA-RC