Mitsubishi Electric PUMY-P250YBM Technical & Service Manual page 123

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

Mixed Method
Connection Examples
(Connecting to 3 Branch boxes)
Total piping length
Farthest piping length (L1)
Permissible
Farthest piping length via branch box (L2)
length
Piping length between outdoor unit and branch boxes
(One-way)
Farthest piping length from the first joint
Farthest piping length after branch box ( )
Total piping length between branch boxes and indoor units d + e + f + g + h + i + j + k + l + m + n + o [ 145 m
In indoor/outdoor section (H)* 1
Permissible
height
In branch box/indoor unit section
difference
In each branch unit (h2)
(One-way)
In each indoor unit (h3)
Number of bends
1
*
Branch box should be placed within the level between the outdoor unit and indoor units.
■ Selecting the Refrigerant Branch Kit
■ Select Each Section of Refrigerant
Piping
(1) Section From Outdoor
Unit to Branch box or
Branch header (A to G)
(2) Sections From Branch
box or Branch header to
Indoor Unit (a to o)
Select the size from the table to the
right.
■ Additional refrigerant charge
OCH760
L1
G
C
H*¹
c
a
b
E
E
E
Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch joint
CMY-Y62-G-E
(1) Refrigerant Piping Diameter In Section From Outdoor Unit to Branch box or Branch header
(Outdoor Unit Piping Diameter)
A
Model
P250
Each
Section of
P300
Piping
B to G
Total down-stream capacity of indoor units
16.1 kW – 22.4 kW
22.5 kW – 36.4 kW
* ø12.7 when connecting the indoor unit for PEFY-P200 or P250.
(2) Refrigerant Piping Diameter In Section From Branch box or Branch header to Indoor Unit (Indoor
Unit Piping Diameter)
Indoor unit series
CITY MULTI
M series
Note:
When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor unit, refer to the
installation manual for the CONNECTION KIT when selecting the pipe size and piping length.
Refer to the same section in the previous page.
A
A
B
B
C
D
F
D
D
h1
d
e
f
g
h
i
j
F
F
F
F
F
F
F
h3
A + G + B + C + D + F + E + a + b + c + d + e + f + g + h + i + j + k + l + m + n + o [
310 m
A + G + a [ 85 m
A + B + C + E + o [ 80 m
A + B + C + D + F + E [ 95 m
B + C + E or G + a [ 30 m
o [ 25 m
H [ 50 m (In case of outdoor unit is set higher than indoor unit)
H [ 40 m (In case of outdoor unit is set lower than indoor unit)
h1 + h2 [ 15 m
h2 [ 15 m
h3 [ 12 m
[ 23
Branch header (4 branches)
CMY-Y64-G-E
Liquid pipe
Gas pipe
ø9.52*
ø22.2
ø12.7
ø25.4
– 16.0kW
36.5 kW –
Model number
Liquid pipe
10 – 50
ø6.35
63 – 140
ø9.52
200
ø9.52
250
ø9.52
15 – 42
ø6.35
50
ø6.35
123
A Outdoor unit
B First joint
C Branch header
D Branch box
E CITY MULTI indoor unit
L2
F M series indoor unit
E
D
h2
k
l
m
n
o
R
F
F
F
F
F
Branch header (8 branches)
CMY-Y68-G-E
(mm)
Model
Liquid pipe
Gas pipe
P250
ø9.52*
ø15.88
P300
ø12.7
P250
ø9.52*
ø19.05
P300
ø12.7
P250
ø9.52*
P300
ø12.7
P300
ø12.7
(mm)
Gas pipe
ø12.7
ø15.88
ø19.05
ø22.2
ø9.52
ø12.7
(mm)
ø22.2
ø25.4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents