8.4

Specifications

8.4.1

Power supply

CAUTION
Safe electrical isolation
Use only 24 VDC power supply units with safe electrical isolation in accordance with IEC
60364-4-41 or HD 384.04.41 (VDE 0100, Part 410), e.g. to PELV standard.
The supply voltage must be within the specified voltage range. Otherwise, malfunction at
the HMI device cannot be ruled out.
Applies to non-isolated plant configurations:
Connect the connection for GND 24 V from the 24 V power supply output to equipotential
bonding for uniform reference potential. You should always select a central point of
termination.
The following table shows the permitted rated voltage and the corresponding tolerance
range.
Rated voltage
+24 VDC
8.4.2

KP300 Basic and KP400 Basic

Weight
Weight without packaging
Display
Type
Active display area
Resolution
Possible colors
Contrast control
Brightness control
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
Tolerance range
19.2 to 28.8 V (–20%, +20%)
KP300 Basic mono PN
Approx. 250 g
KP300 Basic mono PN
LCD mono FSTN
87 x 31 mm (3.6")
240 x 80 pixels
4 (only backlighting:
white, red, green, yellow)
Yes
No
Technical specifications
8.4 Specifications
KP400 Basic color PN
Approx. 510 g
KP400 Basic color PN
LCD TFT
95 x 53.8 mm (4.3")
480 x 272 pixels
256
No
Yes
131