Status indication
During startup, status indication takes place according to the following table:
Legend
.... Fixed activation
¡ Off
Red
Yellow
l
Green
n
Operation, instructions, diagnostics
(continued from previous page)
Diagnostics of the cause of fault
After lockout the red fault signal light will remain fixed on.
In this condition visual diagnostics of the cause of fault ac-
cording to the error code table can be activated by holding
down the lockout reset button for more than 3 seconds.
Holding down the reset button again for at least 3 sec-
onds, interface diagnostics will be activated
Color code table for multicolor signal
lamp (LED)
2 blinks
l l
3 x blinks
l l l
4 blinks
l l l l
5 blinks
l l l l l
6 blinks
l l l l l l
7 blinks
l l l l l l l
8 x blinks
l l l l l l l l
9 blinks
l l l l l l l l l
10 blinks
l l l l l l l l l l
During the time the cause of fault is diagnosed, the control outputs are deactivated
- Burner remains shut down
- External fault indication remains deactivated
- Fault status signal "AL" at terminal 10, according to the error code table
To exit from the diagnostics of the cause of fault and switch on the burner again, reset the burner control.
Hold down the lockout reset button for about 1 second (< 3 seconds).
Color code table for multicolor signal lamp (LED)
Status
Waiting time "tw", other waiting states
Ignition phase, controlled ignition
Operation, flame O.K.
Operation, flame not O.K.
Extraneous light upon burner startup
Low voltage
Breakdown, alarm
Error code generation (see "Error code table")
Interface diagnostics
Blocked position
Error code table
«AL» at term. 10
Possible cause
No flame at the end of the "TSA" (safe ignition time)
- Faulty or soiled fuel valves - Faulty or soiled flame detector
On
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
defective "LP" (air pressure switch)
- No or faulty air pressure signal after completion "t10"
On
- "LP" is welded in normal position
Extraneous light upon burner startup
On
On
Time-out "LP" - "LP" is welded into working position
On
Unused
Too many losses of flame during operation (limitation of repetitions)
On
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner
On
Unused
On
Unused
Off
Wiring error or internal error, output contacts, other faults
19 / 26
0006081483_201512
Color code
¡...............................................
l
¡
l
¡
l
¡
l
¡
l
¡
¡...............................................
n
¡
n
¡
n
¡
n
¡
n
¡
n
n
n
n
n
l
l
l
l
l
...............................................
¡
¡
¡
¡
Blocked position
Visual diagnostic
Code error table
Color
Off
Flashing yellow
Green
Flashing green
Green-red
Yellow-red
Red
Flashing red
Flashing red light
Blocked position
PC/analyzer
Diagnostic
interface

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Tbg 60 pn-v1729001517290020

Table of Contents