baltur TBG 120 P Installation, Use And Maintenance Instruction Manual page 64

Two-stage gas burners
Hide thumbs Also See for TBG 120 P:
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
EXPECTED LIFESPAN
The expected lifespan of burners and relevant components depends very much from the type of application on which the burner is installed, from
cycles of delivered power, from the conditions of the environment in which it is located, from maintenance frequency and mode, etc.
Standards about safety components provide for a project expected lifespan expressed in cycles and/or years of operation.
Such components ensure the correct operation in standard (*) operating conditions, with periodic maintenance according to the instructions
contained in the manual.
The table below shows the project expected lifespan of the main safety components; approximately, operating cycles correspond to the burner
activations.
When this expected lifespan limit has almost been reached the component must be replaced with an original spare part .
IMPORTANT
warranty conditions (laid down in contracts and/or delivery or payment notes, if necessary) are independent and do not refer to the
expected lifespan stated below.
(*) "Normal" operating conditions means applications on water boilers and steam generators or industrial applications compliant with the standard
EN 746, in environments with temperatures within the limits provided for in this manual and with pollution degree 2 in compliance with annex M
of the standard EN 60335-1.
Safety component
Control box
Flame sensor (1)
Seal control
Gas pressure switch
Air pressure switch
Gas pressure regulator (1)
Gas valves (with seal check)
Gas valves (without seal check) ( 2)
Servomotors
Liquid fuel hoses
Liquid fuel valves
Air fan impeller
(1) The characteristics can degrade over time; during the annual maintenance the sensor must be checked and in case of flame signal degradation
must be replaced.
(2) Using normal mains gas.
Project expected lifespan
Operating cycles
250 000
N.A.
250 000
50 000
250 000
N.A.
Until the first seal fault signal
250 000
250 000
N.A.
250 000
50,000 activations
28 / 34
0006081521_201711
Years of operation
10
10,000 operating hours
10
10
10
15
10
10
5 (every year for fuel oil burners or in the presence
of biodiesel in diesel/kerosene)
10
10