ENGLISH
SERVOMOTOR CAM SQN72.X4A20 FOR TBG...P REGULATION
1
I
2nd flame air regulation cam (85°)
II
Total air closure (burner stopped) (0°)
III
1st flame air regulation cam (20°)
IV Cam not used
V
Ignition transformer cam (30°)*
* CAM V >III (approximately 5° / 10°)
To adjust the setting of the cams used, use the corresponding rings
(I - II - III). The scale on the ring indicates the reference scale of the
rotation angle set for each cam.
3
2
1
Reference scale
2
Position indicator
3
Camshaft-motor coupling insertion and exclusion pin.
4
Adjustable camshaft
24 / 34
0006081521_201711
4