MALFUNCTION AND LOCK CAUSE DIAGNOSTICS.
In the event of a burner lock-out, the red light on the reset button will be fixed.
Keeping it pressed in for more than 3 seconds, the diagnostics procedure is activated (red light with quick flashes). The table below indicates the
meaning of the lock-out or failure according to the number of red flashes.
Holding the reset button down for at least 3 seconds, the diagnostics function will be interrupted.
The diagram below shows the operations to be carried out to activate the diagnostic functions even with communication interface through the
"OCI400" connection cable.
Operating position
O n
E K
> 3 s
Visual indication
AL to terminal 10
2 blinks
On
●●
3 blinks
On
●●●
4 blinks
On
●●●●
5 blinks
On
●●●●●
6 blinks
On
●●●●●●
7 blinks
On
●●●●●●●
8 blinks
On
●●●●●●●●
9 blinks
On
●●●●●●●●●
10 blinks
On
●●●●●●●●●●
14 blinks
On
●●●●●●●●●●●●●●
• During the time the cause of fault is diagnosed, the control outputs are deactivated.
• - Is the burner shut down
• - The alarm signal AL "is on terminal 10 which is under voltage.
• Press the lockout reset button for about 1 second (< 3 seconds) to reactivate the device and start a new cycle.
Operating position
Visual indication
E K
Colour code table
> 3 s
x x x x xx x x
x x x x xx x x
x x x x xx x x
x x x x xx x x
x x x x xx x x
x x x x xx x x
Possible causes
No flame at the end of the safe ignition time<TSA>
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- No ignition Faulty ignition transformer
- Defective LP air pressure switch
- No or faulty air pressure signal after completion "t10"
- LP pressure switch contact welded in standby position
Extraneous light during the ignition phase
- No air pressure switch signal
- LP pressure switch contact welded in work position
Not used
No flame signal during normal operation, ignition repetition (limitation of ignition
repetitions)
- Malfunction of the fuel valves
Faulty or soiled flame detector
- Poor adjustment of burner
Not used
Not used
Wiring problems or damage inside the device
CPI contact not closed
22 / 34