baltur TBG 120 P Installation, Use And Maintenance Instruction Manual page 50

Two-stage gas burners
Hide thumbs Also See for TBG 120 P:
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
CAUTION / WARNING
The housings for the cables for the plugs are provided
respectively for cable Ø 9.5÷10 mm and Ø 8.5÷9 mm, this
ensures the protection rating is IP 54 (Standard IEC EN60529)
for the electrical panel.
• To reclose the electrical panel lid, fix the screws (1) with a torque of
about 5 Nm to ensure the correct seal.
To gain access to the control panel (8), slide the transparent door
(7) for a short distance following the direction on the arrow indicated
in the figure exerting slight pressure with a tool (e.g. a screwdriver)
following the arrows' direction and slide it for a short distance to
separate it from the cover.
• To secure the transparent door on the panel properly, position the
hooks at their hooking points (9), slide the door in the direction
indicated by the arrow until you hear a click that ensures its seal.
CAUTION / WARNING
Only professionally qualified personnel may open the burner
electrical switchboard.
• In case of unbalanced 230V phase-phase mains supply systems,
the voltage between the flame detector electrode and earth might
not be enough to ensure the correct operation of the burner. The
problem is eliminated using the isolation transformer type AR1
code 0005020028 which must be connected as shown in the
following diagram.
AR 1
Ph
L (1)
ION IN
Ph 230
IN (2)
ION PROBE
ION
14 / 34
0006081521_201711
8
7
9
9
9
9

Advertisement

Table of Contents
loading

Table of Contents