baltur TBG 120 P Installation, Use And Maintenance Instruction Manual page 55

Two-stage gas burners
Hide thumbs Also See for TBG 120 P:
Table of Contents

Advertisement

Available languages

Available languages

AIR REGULATION ON THE COMBUSTION HEAD
The combustion head has a regulation device that allows the air
passage between the disc and the combustion head to be opened or
closed. Closing the passage, you can obtain high pressure upstream
of the disc even at low flow rate. The high speed and turbulence of
the air provides for its greater penetration into the fuel and therefore
an excellent mixture and flame stability. High air pressure upstream
of the disc may be necessary to prevent flame fluctuations, this is
particularly essential when the burner works on the combustion
chamber that is pressurised and/or at a high thermal load.
CAUTION / WARNING
Check that the combustion head is centred with respect to the
disk. An imperfect centring could cause a poor combustion and
overheating of the head with its subsequent rapid deterioration.
CAUTION / WARNING
The above adjustments are indicative only; position the
combustion head according to the characteristics of the
combustion chamber.
BURNER
TBG 120P
17 ÷ 54
TBG 150P
17 ÷ 36
TBG 210P
14 ÷ 51
• Loosen the screw (1)
• Turn screw (2) to position the combustion head (3), referring to
index (4)
• Adjust the distance (x) between the minimum and maximum
according to the indications in the table
Value indicated by
X
index 4
1 ÷ 5
1 ÷ 3.2
1 ÷ 5
0006081521_201711
19 / 34
ENGLISH