baltur GI MIST 1000 DSPGM Instruction Manual page 58

Progressive/modulating two-stage mixed gas/diesel burners
Table of Contents

Advertisement

Available languages

Available languages

DETAIL OF BURNER WITH ATOMIZER UNIT, MODULATION SERVOMOTOR, RETURN PRESSURE
REGULATOR, AIR GATE REGULATOR WITH LPG OR NATURAL GAS PILOT BURNER
CONNECTION TO POWER
SUPPLY CIRCUIT SEE
0002901120 FOR ONE
OR MORE BURNERS
100 mbar PILOT GAS RAMP INLET
RETURN PRESSURE REGULATOR
MIN = 10 + 12 bar
MAX = 18 + 20 bar
1
FILTER
2
BURNER PUMP (20-22 BAR)
3
PRESSURE GAUGE O-40 BAR
4
ATOMIZER BODY
5
RETURN NOZZLE WITHOUT PIN
6
RODS WITH CLOSING PINS
7
BY-PASS HOLES
8
CLOSING SPRINGS
9
OPENING ELECTROMAGNET
10 RETURN PRESSURE REGULATOR
11 MODULATION SERVOMOTOR
12 AIR/FUEL REGULATION CONTROL DISC
13 AIR GATES
14 HOSE
15 IGNITION PILOT
16 MAIN GAS VALVE FOR IGNITION FLAME WITH FLOW CONTROL
(PILOT FLAME)
17 SAFETY GAS VALVE FOR IGNITION (PILOT) FLAME
18 MINIMUM AND MAXIMUM GAS PRESSURE SWITCH PILOT RAMP
19 PRESSURE CONTROL WITH BUILT-IN FILTER
20 NOZZLE RETURN THERMOSTAT (NRT) ONLY FOR FUEL OIL
BURNER MODELS
14 / 42
0006080764 _201312
FOR VERSION ...D
THERMOSTAT T R U
MIN= 10-12 BAR
MAX= 18-20 BAR