Auxiliary Set Up Group

Introduction

The Auxiliary group lets you configure the Auxiliary Output to be a specific selection with desired
scaling.
Accutune III automatically calculates GAIN, RATE, and RESET TIME (PID) tuning constants for
your control loop. When initiated on demand, the Accutune algorithm measures a process step
response and automatically generates the PID tuning constants needed for no overshoot on your
process. It operates with PIDA, PIDB, PD+MR and Three Position Step Control Algorithm.

Function Prompts

Set up
Function
Group
Prompt
DIG IN
Auxiliary
ACCUTUN
E
Revision 2.0
July 2015
7-Segment
Code
Default
Value
DIN
None
AT
Disable
EDC201 / EDC202 / EDC203 Product Manual
Selection
7-Segment
or Range
Code
of
Setting
NONE
NONE
AM
A|M
DIR
Direction
LOCK
LOCK
TMR
Timer
ACK
ACK
AT
AT
DISB/ TUNE
DISABLE
3. Configuration
3.8. Auxiliary Set Up Group
Parameter
Definition
NO DIGITAL INPUT
SELECTIONS
Switch Automatic /Manual
operating mode.
The controller will scan the
current action direction and
redirect to the opposite
direction.
KEYBOARD LOCKOUT.
Contact closure disables
all keys.
The timer is started once
the rising-edge of a digital
input is detected.
Alarm acknowledgement
configuration. The system
acknowledges the alarm
once the rising edge of
digital input is detected.
ON/OFF the ACCUTUNE.
If the rising-edge of a
digital input is detected, the
system will start Accutune
if the start condition has
been met and Accutune is
not running.
Disables the Accutune
function.