3. Configuration
3.7. ALARM Set Up Group
Set up
Function
Group
Prompt
Top Display
22SEL
22VAL
ALHYST
ALARM
DELAY
34
7-Segment
Default
Code
Value
Upper Display
SE22
VL22
HYSA
1%
DLYA
0
EDC201 / EDC202 / EDC203 Product Manual
Selection or
7-Segment
Range of
Code
Setting
Lower Display
DIAG
Diagnostic
HI
HIGH
LO
LOW
-
-
0-100% OF
SPAN
0 ~ 30s
Parameter
Definition
SYSTEM
DIAGNOSTIC. This
configuration is not
available on EDC201.
HIGH ALARM. This
configuration is not
available on EDC201.
LOW ALARM. This
configuration is not
available on EDC201.
ALARM 22 SET
POINT VALUE。This
configuration is not
available on EDC201.
ALARM
HYSTERESIS—A
single adjustable
hysteresis is provided
on alarms such that
when the alarm is OFF
it activates at exactly
the alarm Set Point;
when the alarm is ON,
it will not deactivate
until the variable is
0.0 % to 100 % away
from the alarm Set
Point.
Configurable alarm
trigger delay time
allows you to force the
trigger time of an alarm
to delay for a time
period of from 0 to 30
seconds in an alarm
condition.
Revision 2.0
July 2015