Advertisement

Quick Links

Technical Information
Series 8 Controller and I/O Specification
S803-150-500
Release 500
July 2017, Version 1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Experion 8 Series

  • Page 1 Technical Information Series 8 Controller and I/O Specification S803-150-500 Release 500 July 2017, Version 1...
  • Page 2 Series 8 Controller and I/O Specification, S803-150-500 Revision History Revision Date Description July 2017 Release version Version 1 July 2017...
  • Page 3: Table Of Contents

    Series 8 Controller and I/O Specification, S803-150-500 Table of Contents Introduction ..................................4 1.1. Overview ................................... 4 1.2. Scope ..................................4 1.3. Definitions ................................. 4 Product Introduction ..............................4 2.1. C300 Controller ................................. 4 2.1.1. Overview ..................................... 4 2.1.2. Model Numbers ................................... 6 2.2.
  • Page 4: Introduction

    Series 8 Controller and I/O Specification, S803-150-500 Introduction 1.1. Overview This document provides technical information to configure the Experion® Series 8 I/O and the C300 Controller. 1.2. Scope The following Series 8 hardware items are included in this document.  ...
  • Page 5 Series 8 Controller and I/O Specification, S803-150-500 contains all of the control and communication functionalities. The C300 IOTA contains only passive devices such as FTE address switches, FTE cable connectors and I/O Link cable connectors. Figure 1 below depicts the IOTA components.
  • Page 6: Model Numbers

    Coated IOM and IOTA are recommended when electronics must withstand harsh environments and need to have added protection. For a quick reference, all the Series 8 Honeywell models starting with 8C denotes ‘with Conformal Coating’ and the models starting with ‘8U’ denotes non-conformal coated hardware.
  • Page 7: I/O Module Functions

    Series 8 Controller and I/O Specification, S803-150-500 Vertical mounting for more effective wiring since most field wiring applications require entry from the top or bottom of the systems cabinet An “information circle” for a quick visual cue to draw the Maintenance Technician’s eye to important status information “Tilted”...
  • Page 8: Series 8 I/O Sizing

    Coated IOM and IOTA are recommended when electronics must withstand harsh environments and need to have added protection. As a quick reference, all the Series 8 Honeywell models starting with 8C denotes ‘with Conformal Coating’ and the models starting with ‘8U’ denotes non-conformal coated hardware.
  • Page 9 Series 8 Controller and I/O Specification, S803-150-500 I/O Module IOTA Description Circuits Size Red. (Coated) (Coated) (in “) 8C-PAIH54 High-level AI HART, Differential √ 8C-TAIDA1 AI IOTA 8C-TAIDB1 AI IOTA Redundant √ 8C-PAIHA1 High-level AI HART, Single-ended √ 8C-PAINA1 High-level AI w/o HART, Single-ended √...
  • Page 10 Series 8 Controller and I/O Specification, S803-150-500 I/O Module IOTA Description Circuits Size Red. (Uncoated) (Uncoated) (in “) 8U-PAIH54 High-level AI HART, Differential / Single- √ ended 8U-TAIDA1 AI IOTA 8U-TAIDB1 AI IOTA Redundant √ 8U-PAIHA1 High-level AI HART, Single-ended √...
  • Page 11: Specifications

    Series 8 Controller and I/O Specification, S803-150-500 Specifications 3.1. Environment Conditions and Approvals 3.1.1. General Environmental Characteristics and Series 8 Information This section relates to the physical characteristics applicable to Series 8 C300 controller and all Series 8 I/O components. Where applicable, specifications state limits within an approved cabinet and to the cabinet skin.
  • Page 12: Approval Bodies

    Series 8 Controller and I/O Specification, S803-150-500 3.1.2. Approval Bodies Approval Body Certification Category Description All models are approved as non-incendive for use in Class I, Division 2 Approvals Division 2, Group A, B, C, D hazardous (classified) locations. All models are approved as normally non-sparking apparatus Factory Manual for use in Class I, Zone 2, AEx nA IIC hazardous (classified) Zone 2 Approvals...
  • Page 13: Detailed Specification- Approvals

    Series 8 Controller and I/O Specification, S803-150-500 3.1.2.1. Detailed Specification- Approvals Consideration Approval Cabinet: Class I, Division 2, Grp. ABCD, T4 Agency Approvals Class I, Zone 2, AEx/Ex nA IIC T4 GC ATEX II 3G Ex nA IIC T4 GC IECEx Ex nA IIC T4 GC Item Specification...
  • Page 14 Series 8 Controller and I/O Specification, S803-150-500 Item Specification Electromagnetic compatibility (EMC) – Part 4-8: Testing and measurement techniques – Power frequency magnetic field immunity IEC61000-4-8 2009 test Electromagnetic compatibility (EMC) – Part 4-11: Testing and measurement techniques – Voltage dips, short interruptions and IEC61000-4-11 2004 voltage variations immunity tests...
  • Page 15: C300 Controller Specifications

    Series 8 Controller and I/O Specification, S803-150-500 3.2. C300 Controller Specifications 3.2.1. C300 Control Execution Environment (CEE) The C300 CEE provides an execution and scheduling environment in which Control Modules (CMs) and Sequential Control Modules (SCMs) execute user-configured control strategies. The CEE also support peer to peer communications with other C300 controllers and communication modules like Foundation Fieldbus and Profibus.
  • Page 16: C300 Supported Function Blocks

    Series 8 Controller and I/O Specification, S803-150-500 Modbus TCP devices PCDI function block Ethernet IP Native peer to peer Optional C300 Memory Backup 51454475-100 Series 8 C300 RAM Charger Module 51202330-300 Cable, Battery RAM charger, 30 in 51202330-200 Cable, Battery RAM charger, 84 in 3.2.3.
  • Page 17 Series 8 Controller and I/O Specification, S803-150-500 Function Block Function Block Function Block Function Block GE (Compare Greater than nOON Step or Equal) Transition GT (Compare Greater Than) STARTSIGNAL Synchronize LE (Compare Less than or OFFDELAY TRIG Handler Equal) ONDELAY WATCHDOG Phase LIMIT...
  • Page 18: Specifications For Series 8 I/O

    Series 8 Controller and I/O Specification, S803-150-500 3.3. Specifications for Series 8 I/O Specifications for Series 8 I/O modules are shown below. Note only the Coated S8 modules (model number starting with 8C) are mentioned in the detailed specifications below. However below specifications apply equally for the uncoated modules as well.
  • Page 19 Series 8 Controller and I/O Specification, S803-150-500 Maximum Normal Mode Input (any input ± 30 Volts referenced to common, no damage) Input Scan Rate 50 ms ± 0.075% of full-scale (23.5°± 2°C) Hardware Accuracy (@ CMV = 0 V) ± 0.15% of full-scale (0 to 60°C) Module Removal and Insertion Supported Under Power...
  • Page 20: Analog Input With Hart - Single Ended

    Series 8 Controller and I/O Specification, S803-150-500 3.3.2. Analog Input with HART – Single Ended Function The Analog Input Module accepts high level current inputs from transmitters and sensing devices. Notable Features   Extensive self-diagnostics On board excitation power (no need for marshalling ...
  • Page 21 Series 8 Controller and I/O Specification, S803-150-500 Galvanic Isolation (any input terminal 1000VAC RMS or ±1000 VDC voltage referenced to common) Isolation Technique Icoupler (in IOM) Module Removal and Insertion Supported Under Power Transmitter Field Power Conditioning Individually Protected Current Limiting Circuits. No fuse required Note 1 –...
  • Page 22: Analog Input - Single Ended

    Series 8 Controller and I/O Specification, S803-150-500 3.3.3. Analog Input – Single Ended Function The Analog Input Module accepts high level current inputs from transmitters and sensing devices. Notable Features   Extensive self-diagnostics On board excitation power (no need for ...
  • Page 23 Series 8 Controller and I/O Specification, S803-150-500 Isolation Technique Icoupler (in IOM) Module Removal and Insertion Supported Under Power Transmitter Field Power Conditioning Individually Protected Current Limiting Circuits. No fuse required Note 1 – No differential / voltage inputs are supported. Note 2 –...
  • Page 24: Low Level Analog (Temperature) Input Llai

    Series 8 Controller and I/O Specification, S803-150-500 3.3.4. Low Level Analog (Temperature) Input LLAI Function The Low Level Analog Input (LLAI) Module accepts up to 16 channels of temperature inputs from RTD & TC. Notable Features   TC and RTD operation Configurable OTD protection (See below) ...
  • Page 25 Series 8 Controller and I/O Specification, S803-150-500 TC, millivolt inputs +/-20 ppm per deg C max Temperature stability RTD inputs +/-20 ppm per deg C max 500 ppm Long term drift 1 megohm at dc (TC only) Input impedance CMV with respect to Power System Channel to Shield :+/-250 VDC or VAC RMS common, dc to 60 Hz Channel to Channel: +/-33 VDC or VAC RMS...
  • Page 26 Series 8 Controller and I/O Specification, S803-150-500 ANSI specification B +100 to +1820 deg C ANSI specification S 0 to +1700 deg C ANSI specification R 0 to +1700 deg C ANSI specification N -13 to +1300 deg C -20 to +100 millivolts Supported millivolt types Note 1 –...
  • Page 27: Analog Output With Hart

    Series 8 Controller and I/O Specification, S803-150-500 3.3.5. Analog Output with HART Function The Analog Output (AO) Module delivers high-level constant current to actuators and recording/indicating devices. Notable Features   Extensive self-diagnostics Safe-state (FAILOPT) behaviors configurable on  a per channel basis Optional redundancy ...
  • Page 28 Series 8 Controller and I/O Specification, S803-150-500 Maximum Open Circuit Voltage 22 V Response Time(DAC input code to Settles to within 1% of final value within 80 ms output) Gap (0 mA) of Output to Field on 10 ms maximum (applies to Redundancy only) Switchover Module Removal and Insertion Supported...
  • Page 29: Analog Output

    Series 8 Controller and I/O Specification, S803-150-500 3.3.6. Analog Output Function The Analog Output (AO) Module delivers high-level constant current to actuators and recording/indicating devices. Notable Features   Extensive self-diagnostics Safe-state (FAILOPT) behaviors configurable on  a per channel basis Optional redundancy Safe-state Behavior (FAILOPT) Series 8 AO module supports the FAILOPT parameter on a per channel basis.
  • Page 30 Series 8 Controller and I/O Specification, S803-150-500 Maximum Open Circuit Voltage 22 V Response Time settles to within 1% of final value within 80 ms (DAC input code to output) Gap (0 mA) of Output to Field on 10 ms maximum (applies to Redundancy only) Switchover Module Removal and Insertion Supported...
  • Page 31: Digital Input 24Vdc

    Series 8 Controller and I/O Specification, S803-150-500 3.3.7. Digital Input 24VDC Function The Digital Input 24VDC accepts 24VDC signals as discrete inputs. Notable Features   Extensive self-diagnostics for data integrity On board excitation power (no need for  marshalling power) Optional redundancy ...
  • Page 32: Digital Input Sequence Of Events

    Series 8 Controller and I/O Specification, S803-150-500 3.3.8. Digital Input Sequence of Events Function The Digital Input Sequence of Events (DISOE) accepts 24VDC discrete signals as discrete inputs. The inputs can be time tagged to support 1ms resolution Sequence of Events Notable Features ...
  • Page 33: Digital Input Pulse Accumulation

    Series 8 Controller and I/O Specification, S803-150-500 3.3.9. Digital Input Pulse Accumulation Function The Digital Input Pulse Accumulation accepts 24VDC signals as discrete inputs. The first 16 channels can be configured either as Digital Input or Pulse accumulation to support Pulse Accumulation and frequency measurement on per channel basis.
  • Page 34: Digital Output 24Vdc

    Series 8 Controller and I/O Specification, S803-150-500 3.3.10. Digital Output 24VDC Function The Digital Output bussed 24VDC (DO24V) module can switch reliable 24V digital output signals to control other process equipment as well as solenoid valves and interposing relays. Notable Features ...
  • Page 35 Series 8 Controller and I/O Specification, S803-150-500 On-State Voltage 24 VDC (typ) (load current @ 0.1A max) Off-State Leak Current 5 µA (max) Turn-On/Turn-Off Time 10 ms (max) Gap (0 current) of Output to Field on None (0ms) (applies to Redundancy only) Switchover Module Removal and Insertion Supported...
  • Page 36: Do Relay Extension Board

    Series 8 Controller and I/O Specification, S803-150-500 3.3.11. DO Relay Extension Board Function The Digital Output Relay provides a dry contact for isolated low voltage / low current or high voltage / high current discrete output applications. Each relay supports a Form-C output contact. The Relay extension board connects the Digital Output 24V (DO24V) IOM with DO IOTA to support the Relay output.
  • Page 37 Under Power Relay Cable assembly Honeywell Part # 51155506-xxx (0.5 mtr to 50 mtr cable length options) Note 1 – The minimum 10mA load current and 5 VDC load voltage specified are only valid if the contact has not been previously used in high current / high voltage applications.
  • Page 38: Series 8 Io Function Matrix

    Series 8 Controller and I/O Specification, S803-150-500 Series 8 IO Function Matrix The following tables assist in selecting I/O Modules and IOTAs with similar functional characteristics: AI Function Matrix Function NR IOTA Red IOTA HART 4-20 mA 8C-PAIHA1 8C-TAIXA1 8C-TAIXB1 ♦...
  • Page 39 Series 8 Controller and I/O Specification, S803-150-500 DI Function Matrix NR IOTA Red IOTA Function ♦ 8C-PDILA1 8C-TDILA1 8C-TDILB1 ♦ 8U-PDILA1 8U-TDILA1 8U-TDILB1 8C-PDISA1 8C-TDILA1 8C-TDILB1 ♦ 8U-PDISA1 8U-TDILA1 8U-TDILB1 ♦ 8C-PDIPA1 8C-TDILA1 8C-TDILB1 ♦ 8U-PDIPA1 8U-TDILA1 8U-TDILB1 ♦ DO Function Matrix Relay NR IOTA Red IOTA...
  • Page 40: Glossary

    The node at the heart of Experion HS. The servers encompasses a wide range of subsystems including history collection, SCADA interfaces, alarm/event, etc. Fail Safe Controller HC900 Honeywell process automation controller Input / Output Local area network based on Ethernet technology Mode...
  • Page 41 Honeywell International Inc. While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer.

Table of Contents