Maintenance Checklist - ABB MNS-Up Service Manual

Hide thumbs Also See for MNS-Up:
Table of Contents

Advertisement

78
M N S - U P S E R V I C E M A N U A L
18.1

Maintenance checklist

Item no.
Work to be performed
1.0
General visual inspection
(repetitive tests)
1.1
External inspection
1.1.1
Verify ambient conditions
1.1.2
Check ventilation system
(efficiency)
– Operating room
– Switchgear system
Check condition of
enclosure/outside paint
1.1.3
– Check condition of
enclosure/outside paint
1.1.4
Accessibility
1.2
Completion of the interior
1.2.1
Equipment compartment
– Check filling factor
and equipment
– Internal conditions
1.2.2
Cable compartment/
cable terminal
compartment
Personal protection/
protective bellows
1.2.3
Busbar compartment
– Check transport
connections
– Check busbar supports
Visual inspection of the
condition of the busbar
insulation
Measured, test and limit
Frequency installation category
values, operating and
A
auxiliary materials
– Room temperature ≤ 35°C
– Air, aggressive gases
1a
such as SO
, H2S etc.
2
– Relative humidity
≤ 50 % at 40°C
– Dust
6m
– Air supply to and air
discharge from section
not obstructed
– max. temperature inside
the section:
≤ 60°C
– Damaged / corroded
1a
– Missing parts such as
module doors or covers
– Ventilation louver dusty/
covered
– Roof plate contaminated/
covered/obstructed/etc.
– Fastening of cable
compartment doors,
side and back panels
– Position of withdrawable
modules in the section
(operating or isolated
position)
– Cable/equipment
compartment doors
closed/open
– Escape route ≥ 650 mm
– Escape route ≥ 650 mm
1a
– Arrangement of modules
1a
in accordance with
engineering documents
– Contamination, e.g. dust
– Incoming feeder in
accordance with
documents (busbar/cable
laterally/top/bottom)
– Sufficient room/strain
relief
– Cable routing; bending
radii
– Protective bellows
– Color changes at bolted
1a
connections
– Proper installation of cover
in partition wall 3
– Contamination or
flashover
– Formation of cracks or
creeping paths
– Shrink-on tube brittle
Remarks
B
C
6m
X
Unpleasant smell
Auxiliary heating possibly
required
6m
X
Touch fronts with hand surface,
check section if hand-warm
spots are found
6m
X
6m
X
6m
X
Clean
6m
X
Check using thermo-vision
exposures

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents