46
M N S - U P S E R V I C E M A N U A L
7.6
Battery connection
Battery connection can be done for each 100kW module individually or one complete section.
Battery connections need to be done before the filter modules are installed in the filter section.
7.6.1
Individual batteries
Battery connection bars are provided for each module level.
Figure 7-09
Individual battery connection
7.6.2
Common batteries
In case a common battery set must be connected to one MNS-Up section, the battery connection bars of the different mod-
ule levels need to be connected using copper links.
Figure 7-10
Common battery connection