T R A N S P O R T
Figure 6-04
Crane transport, transport unit in box
6.2

MNS-Up Modules

The MNS-Up active and passive modules must be shipped in their original packing. Stacking of boxes is allowed, up to two
boxes.
6.3

Circuit breakers

Circuit breaker must be treated in the following way:
Fixed circuit breaker must be additionally braced. The bracing must be removed prior to commissioning.
Withdrawable air circuit breaker and withdrawable molded case circuit breaker with rated current of more than 1000 A must
be removed and packed separately in their original packaging.
Heavy busbar constructions must be supported during transport in an adequate way. It is important to attach a caution label
requiring the removal of the used transport fixing material during switchgear erection.
Separately shipped circuit breakers are to be inserted in accordance with the operating instructions of the manufacturer
included in the boxes of the devices.
Stacking of boxes may be restricted by the original supplier of the equipment. This is clearly marked on the transport boxes.
Figure 6-05
Frame corner joint with lifting angle
39